Alarm Hysteress

You can set a width (hysteresis) to the values used to activate and release alarms.
Alarm hysteresis prevents frequent activation and release of alarms when the measured/
computed value is unstable around the alarm value.

Alarm value

Alarm reset

Alarm occurrence

Upper limit alarm

Lower limit alarm

Measured value

or computed value

Alarm reset

Hysteresis

Alarm value

Alarm occurrence

Measured value

or computed value

Alarm Indcaton on the Numercal Dsplay

Four alarm signals are displayed above the value (see the figure below). The changes in
the color of these alarm signals indicate the alarm status.

Alarm 1 status

Alarm 2 status

Alarm 3 status

Alarm 4 status

Black: Alarm not set

Green: Alarm OFF

Red: Alarm occurrence

Note

When using computation channel alarms, do not disconnect the MX100 and the PC software.
Computation channel alarms will not occur because the computation function does not work
when using only the MX100.

2.9 Settng Alarms and Alarm Indcatons