1.2 Communication Functions Using the RS-

422A/485 Communication Interface (/C3

Option)

The recorder can be equipped with an optional RS-422A/485 communication interface.
For details on how to use the RS-422A/485 communication interface, see chapter 3.

Functional Construction

The following figure shows the relationship between the communication function of
the recorder and the RS-422A/485 communication interface. Perform communication
according to the respective protocol.

* Protocol is a set of rules that two computers use to communicate via a communication line (or

network).

PC

Connect the recorder and the

PC using a serial cable.

Setting/Measurement Server

Dedicated protocol

Protocol

Interface

RS-422A/485

Modbus Slave

Modbus protocol

Communication functions of the recorder

Application

Setting/Measurement Server

The functions are the same as those of the Setting/Measurement server of the Ethernet
interface. See page 1-1.

<Related Topics>

• RS-422A/485 communication interface settings: Section 3.5
• Commands: Section 4.2
• RS-422A/485 dedicated commands: Section 4.8
• Data output format: Chapter 5

Modbus Slave

• The Modbus protocol can be used to read the measured/computed data on your PC

by reading the input registers of the recorder. The communication input data can be
written or read by writing/reading the hold register of the recorder.

• For details on the Modbus function codes that the recorder supports, see section 3.4.
• This function can be used only when communicating via the serial interface (option).
• For a description on the settings required in using this function, see section 3.5.

Data from slave device

Data to slave device

Modbus master device

Modbus slave device

Serial communication

Recorder