Sn sets the unit – Yokogawa µR20000 User Manual

Page 55

Advertising
background image

4-12

IM 04P01B01-17E

4.4 Setting Commands

p4 Alarm type

H High limit alarm
L Low limit alarm
h Difference high limit alarm
l Difference low limit alarm
R High limit on rate-of-change alarm
r Low limit on rate-of-change alarm
T Delay high limit alarm
t Delay low limit alarm
(Characters are case-sensitive.)

p5 Alarm value
p6 Relay output

ON

Relay ON

OFF

Relay OFF

p7 Relay number (µR10000: I01 to I06,

µR20000: I01 to I06, I11 to I16, I21 to I26,
I31 to I36)

Query

SA[p1[,p2]]?

Example Set a high limit alarm (alarm value = 1000) on

alarm number 1 of channel 02 and output to
relay I01.
SA02,1,ON,H,1000,ON,I01

Description • When the input range is set to SKIP (SR

command), p3 cannot be turned ON.

• The alarm settings are all turned OFF for the

following cases.
• When the input type is changed (VOLT, TC,

etc).

• When the range type is changed.
• When the span and scaling values are

changed during linear scaling (includes
changing the decimal position).

• The h and l settings of p4 are valid only when

the measurement range is set to computation
between channels.

• The hysteresis of alarm ON/OFF (valid when

p4 is H or L) is set using the XA command.

• If p4 is set to R or r, set the interval for the

high/low limit on the rate-of-change using the
XA command.

• The T and t settings of p4 can be specified

when the alarm delay function is enabled (UF
command).

• If p4 is set to T or t, set the alarm delay time

for the delay high/low limit alarm using the BD
command.

• Parameter p5 for the high limit alarm/low limit

alarm and delay high limit alarm/delay lowlimit
alarm
• For DC voltage, TC, and RTD input:

Values within the measurable range in the
specified range (example: –2.000 to 2.000
V for the 2 V range).

• For ON/OFF input (DI): 0 or 1.
• For scaling (1-5V, scaling, and square root):

−5 to 105% of the scale span (except within
−20000 to 30000).

• Parameter p5 for the difference high limit

alarm/difference low limit alarm: Values in the
measurable range can be specified (example:
–1760.0 to 1760.0°C for the TC type R).

• Parameter p5 for the high limit on rate-of-

change alarm/low limit on rate-of-change
alarm: A value greater than or equal to
1 digit can be specified. For example, 1
digit corresponds 0.001 for the 2 V range
(measurable range: –2.000 to 2.000 V). The
maximum value that can be specified is the
width of the measurable range (4.000 V for 2
V range). For ON/OFF input, only “1” can be
specified.

• On models with the computation function (/M1

option), alarms can be set on computation
channels.
• When the computation equation setting (SO

command) is turned OFF, p3 cannot be
turned ON.

• For computation channels, the alarm types

that can be specified are H (high limit
alarm), L (low limit alarm), T (delay high
limit alarm), and t (delay low limit alarm).
T and t can be specified when the alarm
delay function is enabled (UF command).

• If p4 is set to T or t, set the alarm delay

time for the delay high/low limit alarm using
the BD command.

• Set p5 within the range –9999999 to

99999999 excluding the decimal using an
integer.

• The alarm ON/OFF hysteresis is set using

the XA command.

• If the computation channel ON/OFF state,

the computing equation, or the span
value is changed, all alarm settings of that
channel are turned OFF.

SN

Sets the unit.

Syntax

SN p1,p2<terminator>
p1 Channel number
p2 Unit string (up to 6 characters)

Query

SN[p1]?

Example Set the unit of channel 02 to M/H.

SN02,M/H

Description • The unit setting is valid on channels set to

1-5V, scaling, or square root.

• For the characters that can be used for the

units, see appendix 1, “ASCII Character
Codes.”

• On models with the computation function

(/M1 option), unit can be set on computation
channels.