3-3

IM 04P01B01-17E

Using

the
RS-422A/485

Communication

Interface

(/C3
Option)

1

2

3

4

5

6

App

Index

WARNING

To prevent the possibility of electric shock, connect the cables with the power
turned OFF.

Note

• Connect the RD pin to the SD (TD) pin on the PC (converter) end and the SD pin to the RD

pin on the PC end.

• The two-wire system can be used only when using the Modbus protocol.

Connection Example with a Host Computer

A connection can be made with a host computer having a RS-232, RS-422A, or RS-485
port.
• In the case of RS-232, a converter is used.
• For recommended converters, see “Serial Interface Converter” on the next page.
• The two-wire system can be used only when using the Modbus protocol. For the

configuration procedure, see section 3.5

• Four-Wire System

Generally, a four-wire system is used to connect to a host computer. In the case of a

four-wire system, the transmission and reception lines need to be crossed over.

Terminator (external) 120 Ω 1/2 W or greater

#

1

Do not connect terminators to #1 through #n

1.

RS-422A/485

terminal on the

recorder

#

2

#

n

(

#

n ≤ 32)

Terminator (external)

Host

computer

SG

RDB( + )

RDA( – )

SDB( + )

SDA( – )

FG

SG

RD B

RD A

SD B

SD A

(SG)

(RD B)

(RD A)

(SDB)

(SDA)

FG

SG

RD B

RD A

SD B

SD A

(SG)

(RD B)

(RD A)

(SDB)

(SDA)

FG

SG

RD B

RD A

SD B

SD A

(SG)

(RD B)

(RD A)

(SDB)

(SDA)

3.2 Terminal Arrangement and Signal Names and the Connection Procedure of the RS-422A/485 Communication Interface