Two-wire system – Yokogawa µR20000 User Manual

Page 32

Advertising
background image

3-4

IM 04P01B01-17E

(The following figure illustrates the case when the host computer’s interface is RS-232.)

Terminator (external) 120 Ω 1/2 W or greater

#

1

Do not connect terminators to #1 through #n

1.

RS-422A/485

terminal on the

recorder

#

2

#

n

(

#

n ≤ 32)

Terminator (external)

SHIELD

RD( + )

RD( – )

TD( + )

TD( – )

FG

SG

RD B

RD A

SD B

SD A

Host

computer

Converter

(SG)

(RD B)

(RD A)

(SDB)

(SDA)

FG

SG

RD B

RD A

SD B

SD A

(SG)

(RD B)

(RD A)

(SDB)

(SDA)

FG

SG

RD B

RD A

SD B

SD A

(SG)

(RD B)

(RD A)

(SDB)

(SDA)

RS-232

• Two-Wire System

Connect the transmission and reception signals with the same polarity on the RS-

422A/485 terminal block. The two-wire system can be used only when using the
Modbus protocol.

Terminator (externally attached) 120 Ω, 1/2 W or more

#1

Do not connect terminator to #1 to #n–1

#2

#n

(#n ≤ 31)

Terminator (externally attached)

Host

computer

SG

RDB( + )

RDA( – )

SDB( + )

SDA( – )

FG

SG

RD B

RD A

SD B

SD A

(SG)

(B)

(A)

(B)

(A)

FG

SG

RD B

RD A

SD B

SD A

(SG)

FG

SG

RD B

RD A

SD B

SD A

(SG)

(B)

(A)

RS-422A/485

terminal on the

recorder

3.2 Terminal Arrangement and Signal Names and the Connection Procedure of the RS-422A/485 Communication Interface