3.1 RS-422A/485 Communication Interface

Specifications

This section describes the RS-422A/485 communication interface specifications.

Item

Specifications

Terminal block type

Number of terminals: 6, terminal attachment screws: ISO

M4/nominal length of 6 mm

Electrical and mechanical

specifications

Complies with the EIA-422A(RS-422A) and

EIA-485(RS-485) standards

Connection

Multidrop

Four-wire system
Two-wire system

1:32
1:31 (Modbus slave protocol)

Transmission mode

Half-duplex

Synchronization

Start-stop synchronization

Baud rate

Select from 1200, 2400, 4800, 9600, 19200, and 38400 [bps].

Start bit

Fixed to 1 bit

Data length

Select 7 or 8 bits

Parity

Select Odd, Even, or None (no parity).

Stop bit

Fixed to 1 bit

Received buffer length

2047 bytes

Escape sequence

Open and close

Electrical characteristics

6 points consisting of FG, SG, SDB, SDA, RDB, and RDA

The SG, SDB, SDA, RDB, and RDA terminals and the

internal circuitry of the recorder are functionally isolated.

The FG terminal is the frame ground.

Communication distance

Up to 1.2 km

Terminal resistance

120 Ω, 1/2 W