Yokogawa µR20000 User Manual

Page 34

Advertising
background image

3-6

IM 04P01B01-17E

For a two-wire system, the host computer must control the transmission driver of the

converter in order to prevent collisions of transmit and received data. When using the
recommended converter, the driver is controlled using the RS (RTS) signal on the
RS-232.

• When Instruments That Support Only the RS-422A Interface Exist in the

System

When using the four-wire system, up to 32 recorders can be connected to a single

host computer. However, this may not be true if instruments that support only the RS-
422A interface exist in the system.

When the instrument that support only the RS-422A interface exist in

the system

The maximum number of connection is 16. Some of YOKOGAWA’s conventional

recorder only support the RS-422A driver. In this case, only up to 16 units can be
connected.

Note

In the RS-422A standard, 10 is the maximum number of connections that are allowed on one
port (for a four-wire system).

• Terminator

When using a multidrop connection (including a point-to-point connection), connect

a terminator only to the recorder on the end of the chain. In addition, turn the
terminator on the host computer ON (see the computer’s manual). If a converter is
being used, turn ON its terminator. The terminator must be attached externally to the
recommended converters.

3.2 Terminal Arrangement and Signal Names and the Connection Procedure of the RS-422A/485 Communication Interface

Advertising
This manual is related to the following products: