6 setting the communication timeout and keepalive, App index – Yokogawa µR20000 User Manual

Page 27

Advertising
background image

2-11

IM 04P01B01-17E

Using

the
Ethernet

Interface

(/C7
Option)

1

2

3

4

5

6

App

Index

2.6 Setting the Communication Timeout and

Keepalive

The communication timeout function and the keepalive function can be configured.

Setup Items

K.Alive

Ethernet

End

Keep alive

On/Off

On/Off

Timeout

Timeout time

Duration

Timeout

Procedure

For a description of the basic operations, see “Basic Key Operations” on page vi.

Entering Basic Setting Mode

Hold down the

MENU

key for 3 seconds to display the Setting mode screen.

Next, hold down both the

(

DISP

) key and the

(

FUNC

) key for 3 seconds to

display the Basic Setting mode screen.

Note

To cancel an operation, press the

ESC key.

Communication Timeout

1.

Press the

key to select

Ethernet and then press the key.

Basic=Ethernet

2.

Press the

key to select

Timeout and then press the key.

Ethernet=Timeout

3.

Press the

key to select

On and then press the key.

Timeout=On

4.

Set the timeout time and then press the key.

The setting complete screen appears.

Key operations
• Use the

key to select the digit for entering a value.

• Use the

key to select the value you wish to enter.

Duration=

Ethernet timeout

Setting complete

5

Press the

ESC key to return to the higher level menu. To save the settings and

exit from Basic Setting mode, proceed to “Saving the Settings.”

* When the key, key, or

CHARACTER key is pressed while holding down the SHIFT key, the operation

is reversed as when the respective key is pressed by itself.