Deltachill ™ chillers, Chillers, Mechanical cooling ec fans extra quiet – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 102

Advertising
background image

DELTACHILL

Chillers

102

Chillers

Technical Manual : 7022932_V1.9_11/2013


Mechanical Cooling EC Fans Extra Quiet

Ambient (°C)

25

30

35

40

Model

Supply Temp

Output

Input

Output

Input

Output

Input

Output

Input

°C

kW

kW

kW

kW

kW

kW

kW

kW

DCF014SX-04AL00

6

147.3

38.3

139.3

41.8

130.6

45.7

121.1

50.1

7

151.7

38.6

143.5

42.1

134.5

46.0

124.8

50.3

8

156.3

38.8

147.8

42.4

138.5

46.3

128.5

50.6

10

165.5

39.3

156.5

42.9

146.8

46.8

136.2

51.2

12

174.9

39.9

165.5

43.4

155.2

47.4

144.0

51.8

14

184.6

40.4

174.6

44.0

163.8

48.0

152.1

52.4

DCF017SX-04AM00

6

169.5

46.1

159.8

50.3

149.3

55.0

138.0

60.1

7

174.5

46.5

164.4

50.7

153.6

55.4

142.0

60.5

8

179.5

46.9

169.2

51.1

158.0

55.8

146.1

61.0

10

189.7

47.7

178.8

52.0

167.0

56.7

154.4

61.9

12

200.2

48.6

188.6

52.9

176.2

57.6

162.9

62.8

14

210.8

49.4

198.6

53.8

185.5

58.6

171.6

63.8

DCF021SX-06BS00

6

217.6

57.4

205.8

62.7

193.0

68.6

179.1

75.1

7

224.1

57.8

212.0

63.1

198.8

69.0

184.5

75.5

8

230.7

58.2

218.3

63.5

204.7

69.4

190.0

75.9

10

244.2

58.9

231.1

64.3

216.8

70.2

201.3

76.8

12

258.1

59.7

244.3

65.1

229.2

71.1

212.8

77.7

14

272.3

60.5

257.7

65.9

241.9

71.9

224.7

78.6

DCF025SX-06BT00

6

249.8

70.0

235.2

76.4

219.5

83.4

202.6

91.3

7

257.0

70.6

242.0

77.0

225.9

84.0

208.5

91.9

8

264.4

71.2

248.9

77.6

232.3

84.7

214.5

92.6

10

279.3

72.4

263.0

78.8

245.4

86.0

226.6

93.9

12

294.6

73.6

277.4

80.2

258.9

87.4

239.1

95.3

14

310.2

74.9

292.0

81.5

272.6

88.8

251.8

96.8



1

Output kW refers to the chilled water duty.

2

Input kW refers to the unit input power (compressor + fans).

3

Duties applicable for chilled water

T between 4 and 8°C.

4

Interpolate for water temperatures between those quoted, do not extrapolate.

5

Water flow rate (l/s) = Output ÷ (Cp x

T)

6

For conditions outside of those quoted please refer to Airedale.