Chillers deltachill, Chillers, Electrical data extra quiet continued – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 77
Chillers
DELTACHILL
™
Chillers
77
Technical Manual :7022932_V1.9_11/2013
Electrical Data Extra Quiet Continued
ELECTRICAL DATA
DCC011DX-04ACC0
DCC013DX-04ACD0
DCC014DX-04ADD0
Unit Data
Nominal Run Amps
(1)
A
76.0
86.1
96.1
Maximum Start Amps
(2)
A
258.0
303.0
313.1
Recommended Mains Fuse Size
A
100
125
125
Mains Supply
VAC
400 V 3 PH 50 Hz
Max Mains Incoming Cable Size
mm²
Direct to Bus Bar
Recommended Permanent Fuse Size
A
16
16
16
Permanent Supply
VAC
230 V 1 PH 50 Hz
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Control Circuit
VAC
24V/230VAC
Evaporator
Pad Heater Rating
W
80
80
80
External Trace Heating
Available (fitted by others)
W
500
500
500
Condenser Fan - Per Fan (AC)
Quantity
4
4
4
Full Load Amps
A
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
Motor Rating
kW
1.27
1.27
1.27
Condenser Fan - Per Fan (EC)
Quantity
4
4
4
Full Load Amps
A
3.9
3.9
3.9
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.56
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
33.0 / 33.0
43.1 / 33.0
43.1 / 43.1
Quantity
1 + 1
1 + 1
1 + 1
Motor Rating
kW
18.8 / 18.8
24.0 / 18.8
24.0 / 24.0
Sump Heater Rating
W
75
75
75
Start Amps (2)
A
215 / 215
260 / 260
260 / 260
Type Of Start
Direct on line
OPTIONAL EXTRAS
Power Factor Correction
Circuit 1 Comp RLA (PFC)
28.5
36.5
36.5
Circuit 2 Comp RLA (PFC)
28.5
28.5
36.5
Nominal Run Amps
A
67.0
75.0
83.0
Maximum Start Amps
A
253.5
298.5
306.5
Compressor Nominal Run Amps
A
28.5 / 28.5
36.5 / 28.5
36.5 / 36.5
Recommended Mains Fuse Size
A
100
125
125
Electronic Soft-start
Nominal Run Amps
A
76.04
86.08
96.12
Maximum Start Amps
A
172.02
199.02
209.06
Recommended Mains Fuse
A
100
125
125
Power Factor Correction & Electronic Soft Start
Nominal Run Amps
A
67.0
75.0
83.0
Maximum Start Amps
A
167.5
194.5
202.5
Compressor Nominal Run Amps
A
28.5 / 28.5
36.5 / 28.5
36.5 / 36.5
Recommended Mains Fuse Size
A
100
125
125
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
5
5
5
Unit Nominal Run Amps
A
81.0
91.1
101.1
Recommended Mains Fuse Size
A
100
125
125
Motor Rating
kW
2.2
2.2
2.2
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
5
5
5
Unit Nominal Run Amps
A
81.0
91.1
101.1
Recommended Mains Fuse Size
A
100
125
125
Motor Rating
kW
2.2
2.2
2.2
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
4.5
4.5
4.5
Unit Nominal Run Amps
A
80.5
90.5
100.6
Recommended Mains Fuse Size
A
100
125
125
Motor Rating
kW
2.2
2.2
2.2
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
6.3
6.3
6.3
Unit Nominal Run Amps
A
82.3
92.4
102.4
Recommended Mains Fuse Size
A
100
125
125
Motor Rating
kW
3
3
3
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.