DELTACHILL
™
Chillers
106
Chillers
Technical Manual : 7022932_V1.9_11/2013
Ambient (°C)
25
30
35
40
Model
Supply Temp
Output
Input
Output
Input
Output
Input
Output
Input
°C
kW
kW
kW
kW
kW
kW
kW
kW
DCF013DR-04ACD0
6
135.8
32.9
129.0
36.1
121.8
39.6
114.1
43.6
7
140.0
33.1
133.1
36.3
125.7
39.8
117.8
43.8
8
144.4
33.3
137.3
36.5
129.7
40.1
121.6
44.0
10
153.3
33.8
145.8
37.0
137.9
40.5
129.3
44.5
12
162.4
34.3
154.6
37.4
146.3
41.0
137.4
45.0
14
171.8
34.8
163.7
37.9
154.9
41.5
145.6
45.5
DCF014DR-04ADD0
6
149.9
38.1
142.6
41.6
134.6
45.5
126.1
49.9
7
154.5
38.3
147.1
41.9
138.9
45.8
130.1
50.2
8
159.3
38.6
151.6
42.1
143.3
46.1
134.3
50.4
10
169.1
39.1
161.0
42.6
152.2
46.6
142.8
51.0
12
179.2
39.6
170.7
43.2
161.5
47.1
151.6
51.6
14
189.6
40.1
180.6
43.7
171.0
47.7
160.7
52.1
DCF015DR-04ADF0
6
163.2
42.2
155.0
46.0
146.2
50.3
136.8
55.1
7
168.3
42.5
159.8
46.3
150.8
50.6
141.2
55.4
8
173.4
42.8
164.8
46.7
155.5
51.0
145.6
55.7
10
184.0
43.4
174.9
47.3
165.2
51.6
154.8
56.4
12
194.9
44.0
185.3
48.0
175.1
52.3
164.3
57.2
14
206.1
44.7
196.1
48.7
185.3
53.0
174.0
57.9
DCF016DR-04AJJ0
6
169.6
44.3
160.8
48.5
151.7
53.2
142.0
58.5
7
175.0
44.6
166.1
48.8
156.6
53.5
146.7
58.8
8
180.5
44.9
171.3
49.1
161.7
53.8
151.5
59.1
10
191.8
45.5
182.1
49.8
172.0
54.5
161.3
59.8
12
203.5
46.2
193.3
50.5
182.7
55.2
171.5
60.6
14
215.5
46.9
204.9
51.2
193.7
56.0
181.9
61.3
DCF018DR-04BJK0
6
197.8
53.9
187.6
59.2
177.0
65.1
165.2
71.4
7
204.0
54.3
193.6
59.6
182.7
65.5
170.4
71.8
8
210.2
54.8
199.6
60.0
188.3
65.9
175.7
72.2
10
223.1
55.7
211.9
60.9
199.8
66.7
186.6
73.0
12
236.3
56.6
224.7
61.9
211.7
67.6
197.7
73.9
14
250.0
57.5
237.6
62.8
223.7
68.4
209.3
74.8
DCF020DR-06BFK0
6
206.6
50.6
196.1
55.6
185.1
61.1
173.4
67.3
7
213.0
51.0
202.3
56.0
191.0
61.5
179.0
67.7
8
219.5
51.3
208.5
56.3
197.0
61.9
184.6
68.1
10
232.8
52.1
221.4
57.1
209.2
62.6
196.3
68.9
12
246.6
52.8
234.6
57.9
221.8
63.4
208.3
69.7
14
260.8
53.7
248.2
58.7
234.9
64.3
220.7
70.5
DCF023DR-06BKK0
6
232.2
58.1
220.4
64.1
208.0
70.7
194.9
78.2
7
239.3
58.5
227.2
64.5
214.5
71.1
201.2
78.6
8
246.6
59.0
234.2
64.9
221.2
71.6
207.5
79.1
10
261.6
59.9
248.6
65.8
235.0
72.4
220.6
79.9
12
277.0
60.8
263.4
66.7
249.2
73.4
234.2
80.9
14
292.8
61.8
278.7
67.7
263.8
74.4
248.1
81.8
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water
T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x
T)
6
For conditions outside of those quoted please refer to Airedale.