Chillers deltachill, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 107
Chillers
DELTACHILL
™
Chillers
107
Technical Manual :7022932_V1.9_11/2013
Ambient (°C)
25
30
35
40
Model
Supply Temp
Output
Input
Output
Input
Output
Input
Output
Input
°C
kW
kW
kW
kW
kW
kW
kW
kW
DCF026DR-06BKL0
6
264.4
69.6
250.9
76.3
236.6
83.7
221.5
92.0
7
272.5
70.2
258.7
76.8
244.1
84.2
228.6
92.6
8
280.8
70.7
266.7
77.3
251.7
84.8
235.9
93.1
10
297.8
71.7
282.9
78.4
267.3
85.9
250.7
94.2
12
315.1
72.8
299.8
79.5
283.5
87.0
266.2
95.4
14
333.4
74.0
317.2
80.7
300.2
88.2
282.1
96.6
DCF029DR-06BLL0
6
291.4
80.9
276.7
88.2
261.0
96.4
244.3
105.6
7
300.4
81.4
285.3
88.8
269.2
97.1
252.1
106.2
8
309.5
82.0
294.1
89.4
277.6
97.7
260.0
106.9
10
328.2
83.2
311.7
90.6
294.6
98.9
276.4
108.2
12
347.0
84.3
330.3
91.9
312.4
100.3
293.4
109.6
14
367.4
85.7
349.5
93.2
330.8
101.6
310.9
110.9
DCF032DR-08BLM0
6
323.9
84.3
307.6
92.0
290.2
100.6
271.6
110.1
7
333.9
84.9
317.2
92.6
299.3
101.2
280.3
110.8
8
344.1
85.5
327.0
93.3
308.6
101.9
289.1
111.5
10
364.9
86.7
346.9
94.6
327.7
103.2
307.1
112.9
12
386.4
88.0
367.5
95.9
347.4
104.6
325.8
114.3
14
408.6
89.3
388.7
97.2
367.6
106.0
345.0
115.7
DCF035DR-08BMM0
6
346.4
91.8
328.8
100.2
310.2
109.5
290.4
119.8
7
357.1
92.6
339.0
101.0
319.9
110.2
299.6
120.6
8
367.9
93.3
349.3
101.7
329.7
111.0
308.9
121.4
10
390.0
94.8
370.5
103.3
349.8
112.6
328.0
123.0
12
412.8
96.3
392.3
104.9
370.7
114.3
347.8
124.7
14
436.4
97.8
414.9
106.5
392.2
116.0
368.0
126.4
DCF039DR-10BMS0
6
399.1
103.8
379.0
113.3
357.5
123.9
334.5
135.7
7
411.5
104.5
390.8
114.1
368.8
124.7
345.2
136.5
8
424.1
105.2
402.9
114.9
380.3
125.5
356.1
137.3
10
449.9
106.7
427.6
116.4
403.8
127.1
378.4
139.0
12
476.5
108.3
453.1
118.0
427.8
128.7
401.4
140.6
14
503.8
109.8
479.3
119.6
453.0
130.4
425.4
142.4
DCF044DR-10BSS0
6
440.0
119.0
417.9
129.9
394.2
142.1
368.8
155.6
7
453.7
119.8
430.9
130.8
406.7
142.9
380.6
156.5
8
467.5
120.6
444.2
131.6
419.3
143.8
392.6
157.4
10
495.9
122.3
471.4
133.4
445.3
145.6
417.3
159.3
12
525.2
124.0
499.6
135.1
471.5
147.3
442.7
161.1
14
555.3
125.8
528.5
137.0
499.4
149.2
469.3
163.1
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water
T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x
T)
6
For conditions outside of those quoted please refer to Airedale.