Technical Manual : 7022932_V1.9_11/2013


Controls

Monitoring

The microprocessor also monitors and displays the following measured parameters:

Supply Water Temperature

Return Water Temperature

Suction Pressure of each circuit

Liquid Pressure of each circuit

Suction Temperature at each circuit

Superheat for each circuit

Alarm Handling

The controller logs and allows viewing of the last 100 conditions recorded in descending
chronological order through the keypad display.

The following conditions will be detected, triggering a visual display:
Common for both circuits (Dual Circuit units):

Low Supply Temperature

Emergency Stop

Water Flow

Pump(s) status

Pump(s) remote start

Volt Free Contact Alarm Indication

Individual for each circuit:
Individual alarms will isolate the affected circuit only.

Compressor Trip

Low Suction Pressure for each circuit

High Liquid Pressure for each circuit

Low Pressure Switch

Compressor Overload

High Compressor Discharge Temperature

Networking

A Local Area Network (

) can be used to connect a number of chiller controllers to

offer intercommunication and sequence control. There is also the facility to allow the
connection of either a computer or modem for local or remote monitoring.

For further

details, please contact Airedale.

CAUTION

When adding to an existing network, please consult Airedale to ensure
strategy compatibility.