Deltachill ™ chillers, Chillers, Mechanical cooling performance ac fans extra quiet – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 96

Advertising
background image

DELTACHILL

Chillers

96

Chillers

Technical Manual : 7022932_V1.9_11/2013


Mechanical Cooling Performance AC Fans Extra Quiet

Ambient (°C)

25

30

35

40

Model

Supply Temp

Output

Input

Output

Input

Output

Input

Output

Input

°C

kW

kW

kW

kW

kW

kW

kW

kW

DCF014SX-04AL00

6

148.9

39.9

141.1

43.3

132.5

47.2

123.1

51.4

7

153.5

40.1

145.4

43.6

136.5

47.4

126.9

51.7

8

158.1

40.3

149.8

43.8

140.7

47.7

130.8

51.9

10

167.5

40.8

158.7

44.3

149.1

48.2

138.7

52.5

12

177.2

41.3

167.9

44.8

157.8

48.7

146.8

53.0

14

187.1

41.8

177.3

45.3

166.7

49.2

155.1

53.6

DCF017SX-04AM00

6

171.9

47.4

162.3

51.5

151.9

56.0

140.8

61.1

7

177.0

47.8

167.1

51.9

156.4

56.4

145.0

61.5

8

182.2

48.1

172.0

52.3

161.0

56.8

149.2

61.9

10

192.7

48.9

181.9

53.1

170.3

57.6

157.8

62.7

12

203.4

49.6

192.0

53.9

179.8

58.5

166.7

63.6

14

214.4

50.4

202.4

54.7

189.5

59.4

175.8

64.5

DCF021SX-06BS00

6

220.0

59.8

208.4

65.0

195.8

70.7

182.1

77.1

7

226.6

60.1

214.7

65.3

201.8

71.1

187.6

77.5

8

233.4

60.5

221.2

65.7

207.8

71.5

193.3

77.9

10

247.2

61.1

234.3

66.4

220.2

72.2

204.9

78.7

12

261.4

61.8

247.8

67.1

232.9

73.0

216.8

79.5

14

276.0

62.6

261.6

67.9

246.0

73.8

229.1

80.3

DCF025SX-06BT00

6

253.3

71.9

238.9

78.1

223.5

85.0

206.8

92.7

7

260.7

72.4

246.0

78.7

230.0

85.6

212.9

93.3

8

268.3

73.0

253.1

79.3

236.7

86.2

219.1

93.9

10

283.7

74.1

267.6

80.4

250.3

87.4

231.7

95.2

12

299.4

75.2

282.4

81.6

264.2

88.7

244.7

96.5

14

315.5

76.4

297.6

82.9

278.4

90.0

257.9

97.8




1

Output kW refers to the chilled water duty.

2

Input kW refers to the unit input power (compressor + fans).

3

Duties applicable for chilled water

T between 4 and 8°C.

4

Interpolate for water temperatures between those quoted, do not extrapolate.

5

Water flow rate (l/s) = Output ÷ (Cp x

T)

6

For conditions outside of those quoted please refer to Airedale.