Deltachill ™ chillers, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 124
DELTACHILL
™
Chillers
124
Chillers
Technical Manual : 7022932_V1.9_11/2013
Electrical Data Free Cool Chiller Regular Quiet Continued
ELECTRICAL DATA
DCF029DR-06BLL0
DCF032DR-08BLM0
DCF035DR-08BMM0
Unit Data
Nominal Run Amps
(1)
A
199.2
217.1
226.0
Maximum Start Amps
A
416.2
489.6
498.5
Recommended Mains Fuse Size
A
250
250
250
Mains Supply
VAC
400 V 3 PH 50 Hz
Max Mains Incoming Cable Size
mm²
Direct to Bus Bar
Recommended Permanent Fuse Size
A
16
16
16
Permanent Supply
VAC
230 V 1 PH 50 Hz
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Control Circuit
VAC
24V/230VAC
Evaporator
Pad Heater Rating
W
100
100
100
External Trace Heating
Available (fitted by others)
W
500
500
500
Condenser Fan - Per Fan (AC)
Quantity
6
8
8
Full Load Amps
A
4.3
4.3
4.3
Locked Rotor Amps
A
15
15
15
Motor Rating
kW
2
2
2
Condenser Fan - Per Fan (EC)
Quantity
6
6
8
Full Load Amps
A
3.9
3.9
3.9
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.56
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
43.1 / 43.1
43.1 / 47.5
47.5 / 47.5
Quantity
2 + 2
2 + 2
2 + 2
Motor Rating
kW
24.0 / 24.0
24.0 / 28.2
28.2 / 28.2
Sump Heater Rating
W
75
75 + 130
130
Start Amps
A
260 / 260
260 / 320
320 / 320
Type Of Start
Direct on line
OPTIONAL EXTRAS
Power Factor Correction
Circuit 1 Comp RLA (PFC)
36.5
36.5
42.8
Circuit 2 Comp RLA (PFC)
36.5
42.8
42.8
Nominal Run Amps
A
172.9
194.5
207.1
Maximum Start Amps
A
396.5
471.8
484.4
Compressor Nominal Run Amps
A
36.5 / 36.5
36.5 / 42.8
42.8 / 42.8
Recommended Mains Fuse Size
A
250
250
250
Electronic Soft-start
Nominal Run Amps
A
199.2
217.1
226.0
Maximum Start Amps
A
312.2
361.6
370.5
Recommended Mains Fuse
A
250.0
250.0
250.0
Power Factor Correction & Electronic Soft Start
Nominal Run Amps
A
172.9
194.5
207.1
Maximum Start Amps
A
292.5
343.8
356.4
Compressor Nominal Run Amps
A
36.5 / 36.5
36.5 / 42.8
42.8 / 42.8
Recommended Mains Fuse Size
A
250
250
250
Condenser Fan - Per Fan (EC Extra Freecooling)
Quantity
6
8
8
Full Load Amps
A
4.5
4.5
4.5
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.86
2.86
2.86
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
12
12
12
Unit Nominal Run Amps
A
211.2
229.1
238.0
Recommended Mains Fuse Size
A
250
250
250
Motor Rating
kW
5.5
5.5
5.5
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
14
14
14
Unit Nominal Run Amps
A
213.2
231.1
240.0
Recommended Mains Fuse Size
A
250
250
250
Motor Rating
kW
7.5
7.5
7.5
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
11.2
11.2
11.2
Unit Nominal Run Amps
A
210.4
228.3
237.2
Recommended Mains Fuse Size
A
250
250
250
Motor Rating
kW
5.5
5.5
5.5
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
14.8
14.8
14.8
Unit Nominal Run Amps
A
214.0
231.9
240.8
Recommended Mains Fuse Size
A
250
250
250
Motor Rating
kW
7.5
7.5
7.5
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.