Deltachill ™ chillers, Chillers, Electrical data extra quiet continued – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 80

Advertising
background image

DELTACHILL

Chillers

80

Chillers

Technical Manual : 7022932_V1.9_11/2013


Electrical Data Extra Quiet Continued

ELECTRICAL DATA

DCC022DX-06AKK0

DCC024DX-06BKL0

DCC025DX-08BKL0

Unit Data

Nominal Run Amps

(1)

A

147.1

167.2

172.2

Maximum Start Amps

(2)

A

329.1

384.1

389.1

Recommended Mains Fuse Size

A

200

200

200

Mains Supply

VAC

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

80

100

100

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

6

6

8

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.27

1.27

1.27

Condenser Fan - Per Fan (EC)

Quantity

6

6

8

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Compressor - Per Compressor

Nominal Run Amps

A

33.0 / 33.0

43.1 / 33.0

43.1 / 33.0

Quantity

2 + 2

2 + 2

2 + 2

Motor Rating

kW

18.8 / 18.8

24.0 / 18.8

24.0 / 18.8

Sump Heater Rating

W

75

75

75

Start Amps (2)

A

215 / 215

260 / 215

260 / 215

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Circuit 1 Comp RLA (PFC)

28.5

36.5

36.5

Circuit 2 Comp RLA (PFC)

28.5

28.5

28.5

Nominal Run Amps

A

129.0

145.0

150.0

Maximum Start Amps

A

315.5

368.5

373.5

Compressor Nominal Run Amps

A

28.5 / 28.5

36.5 / 28.5

36.5 / 28.5

Recommended Mains Fuse Size

A

200

200

200

Electronic Soft-start

Nominal Run Amps

A

147.1

167.2

172.2

Maximum Start Amps

A

243.1

280.1

285.1

Recommended Mains Fuse

A

200

200

200

Power Factor Correction & Electronic Soft Start

Nominal Run Amps

A

129.0

145.0

150.0

Maximum Start Amps

A

229.5

264.5

269.5

Compressor Nominal Run Amps

A

28.5 / 28.5

36.5 / 28.5

36.5 / 28.5

Recommended Mains Fuse Size

A

200

200

200

Standard Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

6.2

6.2

6.2

Unit Nominal Run Amps

A

153.3

173.4

178.4

Recommended Mains Fuse Size

A

200

200

250

Motor Rating

kW

3

3

3

Larger Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

8.9

8.9

8.9

Unit Nominal Run Amps

A

156.0

176.1

181.1

Recommended Mains Fuse Size

A

200

200

250

Motor Rating

kW

4

4

4

Standard Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

6.3

8.0

8.0

Unit Nominal Run Amps

A

153.4

175.2

180.2

Recommended Mains Fuse Size

A

200

200

250

Motor Rating

kW

3

4

4

Larger Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

8

11.2

11.2

Unit Nominal Run Amps

A

155.1

178.4

183.4

Recommended Mains Fuse Size

A

200

200

250

Motor Rating

kW

4

5.5

5.5

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.

(2) Starting amps refers to the direct on line connections.