Standard features, Controls, Chillers deltachill – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 13

Advertising
background image

Chillers

DELTACHILL

Chillers

13

Technical Manual :7022932_V1.9_11/2013

Controls

Standard Features

Unit Remote ON/OFF Disables/Enables the Chiller remotely.

Compressor Anti
Cycle Control

Automatic via the Microprocessor.

Compressor Load
Limit

Limits the condensing pressure by unloading above 40Barg.

Limits the evaporating pressure by unloading at the minimum pressure setpoint, which is,
adjustable depending on system glycol content.

Pump(s) Remote
ON/OFF

Disables/Enables the pump(s) remotely.

Remote Setback
Temperature Setpoint
Switch

A setback setpoint for supply water temperature can be selected to suit summer/winter
conditions or night setback.

Compressor Hours
Run

Displays hours run of each compressor.

Password Protection The control system integrity can be maintained by restricting access with a password

PIN number.

CAUTION

IMPORTANT: To change the PIN number; please contact Airedale at time of
order with the preferred 4 digit number.

Controls


Optional Features

Pump(s) Hours Run

Displays hours run of each pump.

BMS Interface Card

Enables

Controlled units to be interfaced with most BMS, factory fitted, please

contact Airedale.

A wide range of protocols can be accommodated through the use of interface devices.
Available as a standard option are: ModBus/Jbus, LonWorks, BACnet and Carel.

For interfaces such as SNMP and Metasys please contact Airedale.

Also available is Airedale’s own supervisory plug-in BMS card pCOWEB.

Based on Ethernet TCP/IP secure technology with SNMP features.

Requires no proprietary cabling or monitoring software and supplied pre programmed with
an IP address for ease of set up.

BMS system configuration by others.