Temperature control, Chillers deltachill – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 23
Chillers
DELTACHILL
™
Chillers
23
Technical Manual :7022932_V1.9_11/2013
Temperature Control
Airedale recognises that all chiller applications are different but fall mainly into 2
application categories; Variable Supply Temperature and Constant Supply Temperature.
The onboard microprocessor has the capability of satisfying either control requirement as
illustrated below.
Using the Airedale Variable Supply Temperature control scheme,
energy savings are available when compared with previous schemes and that of the
Constant Supply Temperature application.
Variable Supply Temperature control schemes offer energy savings where the supply
water temperature is not critical to its operation.
Selection of the best application control scheme can be made via a soft switch in the
microprocessor during initial commissioning.
The microprocessor maintains the set supply Chilled Water temperature by sensing the
return and supply water temperatures and ambient air temperature and adjusting the
compressor loading as required.
Examples based on Model DCC033DR-08BMM0 having 6 Stages of Cooling
Key:
1
Return Water Temperature
2
Mean Value
3
Supply Water Temperature
4
Compressor Off
Variable Supply
Temperature Control
Wa
te
r Te
m
pe
ratu
re
°C
6
7
8
9
10
11
12
13
14
1
3
4
2
20% / 1
40% / 2
50% / 3
60% / 4
80% / 5
100% / 6
Chiller Capacity % / Cooling Stage Sequence
Constant Supply
Temperature Control
Wa
te
r Te
m
pe
ratu
re
°C
6
7
8
9
10
11
12
13
14
20% / 1
40% / 2
50% / 3
60% / 4
80% / 5
100% / 6
1
3
Chiller Capacity % / Cooling Stage Sequence
CAUTION
Factory set to Variable Supply Temperature Control unless otherwise stated
at order.
Only when the mode selection has been set can the unit be enabled.