Deltachill ™ chillers, Chillers, Cooling performance ac fans – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 28
DELTACHILL
™
Chillers
28
Chillers
Technical Manual : 7022932_V1.9_11/2013
Cooling Performance AC Fans
Ambient (°C)
25
30
35
40
Model
Supply Temp
Output
Input
Output
Input
Output
Input
Output
Input
°C
kW
kW
kW
kW
kW
kW
kW
kW
DCC022DR-06AKK0
5
235.7
58.3
223.9
63.7
211.3
69.6
198.1
76.2
6
243.2
58.6
231.0
63.9
218.2
69.9
204.6
76.5
7
250.9
58.9
238.3
64.2
225.1
70.1
211.2
76.7
8
258.6
59.2
245.8
64.5
232.2
70.4
217.9
77.0
9
266.5
59.5
253.3
64.8
239.4
70.7
224.7
77.3
10
274.5
59.8
261.0
65.1
246.7
71.0
231.7
77.5
DCC024DR-04BKL0
5
252.5
70.4
238.6
76.7
223.8
83.8
208.0
91.5
6
260.1
70.8
245.8
77.2
230.6
84.3
214.5
92.0
7
267.8
71.3
253.2
77.7
237.6
84.8
221.0
92.5
8
275.7
71.8
260.3
78.3
244.6
85.3
227.6
93.0
9
283.6
72.3
268.2
78.7
251.8
85.8
234.3
93.6
10
291.7
72.8
275.9
79.2
259.0
86.3
241.1
94.1
DCC025DR-06BKL0
5
264.9
68.1
251.5
74.1
237.2
80.7
221.9
88.0
6
273.2
68.4
259.4
74.4
244.7
81.0
229.0
88.3
7
281.6
68.7
267.5
74.7
252.4
81.3
236.3
88.6
8
290.2
69.1
275.7
75.0
260.2
81.7
243.7
89.0
9
298.9
69.4
284.0
75.4
268.1
82.0
251.2
89.3
10
307.7
69.8
292.5
75.7
276.2
82.4
258.8
89.7
DCC027DR-04BLL0
5
276.3
81.2
261.0
88.3
244.5
96.1
226.7
104.6
6
284.6
81.8
268.8
88.9
251.8
96.7
233.6
105.2
7
292.9
82.3
276.7
89.5
259.3
97.3
240.5
105.8
8
301.4
82.9
284.0
90.2
266.8
97.9
247.6
106.4
9
310.0
83.5
292.9
90.7
274.5
98.5
254.7
107.1
10
318.7
84.1
301.1
91.3
282.2
99.1
262.0
107.7
DCC028DR-06BLL0
5
291.2
77.7
276.6
84.4
260.8
91.6
243.8
99.7
6
300.2
78.1
285.3
84.7
269.0
92.0
251.5
100.1
7
309.4
78.5
294.1
85.1
277.4
92.4
259.4
100.5
8
318.8
78.8
303.0
85.5
285.9
92.8
267.4
100.9
9
328.3
79.2
312.1
85.9
294.5
93.2
275.5
101.3
10
337.9
79.6
321.3
86.3
303.2
93.7
283.7
101.7
DCC030DR-06BLM0
5
315.7
84.7
299.4
91.9
281.9
99.9
263.2
108.6
6
325.4
85.2
308.7
92.4
290.7
100.4
271.4
109.1
7
335.2
85.6
318.1
92.9
299.6
100.9
279.7
109.6
8
345.2
86.1
327.6
93.4
308.6
101.4
288.2
110.2
9
355.4
86.6
337.3
94.0
317.8
102.0
296.8
110.7
10
365.7
87.1
347.1
94.5
327.1
102.5
305.6
111.3
DCC031DR-08BLM0
5
324.1
83.9
308.8
91.0
291.7
98.7
273.3
107.1
6
334.4
84.3
318.5
91.4
301.0
99.1
282.1
107.5
7
344.8
84.6
328.4
91.8
310.4
99.5
291.0
107.9
8
355.5
85.0
338.5
92.2
320.0
99.9
300.0
108.3
9
366.3
85.4
348.8
92.6
329.8
100.3
309.3
108.8
10
377.2
85.8
359.2
93.0
339.7
100.7
318.6
109.2
DCC032DR-06BMM0
5
336.7
91.5
319.1
99.4
300.2
107.9
280.1
117.3
6
346.9
92.1
328.8
100.0
309.4
108.6
288.6
118.0
7
357.2
92.7
338.6
100.6
318.7
109.2
297.4
118.6
8
367.8
93.3
348.6
101.2
328.2
109.8
306.3
119.3
9
378.5
93.9
358.8
101.9
337.7
110.5
315.3
120.0
10
389.3
94.5
369.1
102.5
347.5
111.2
324.4
120.7
DCC033DR-08BMM0
5
347.0
90.1
329.8
97.8
311.4
106.1
291.6
115.2
6
357.7
90.6
340.1
98.3
321.2
106.6
300.9
115.7
7
368.7
91.0
350.6
98.8
331.1
107.1
310.2
116.2
8
379.8
91.5
361.2
99.2
341.2
107.6
319.8
116.7
9
391.2
92.0
372.1
99.7
351.5
108.1
329.4
117.2
10
402.7
92.4
383.0
100.2
361.9
108.6
339.3
117.8
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water
T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x
T)
6
For conditions outside of those quoted please refer to Airedale.