Technical Manual : 7022932_V1.9_11/2013


Installation Data


Positioning

The installation position should be selected with the following points in mind:

Position on a stable and even base, levelled to ensure that the compressor
operates correctly

Levelling should be to +/- 5mm

Where vibration transmission to the building structure is possible, fit spring anti-
vibration mounts and flexible water connections

Observe airflow and maintenance clearances

Pipework and electrical connections are readily accessible

Where multiple units are installed, due care should be taken to avoid the discharge
air from each unit adversely affecting other units in the vicinity

Within a side enclosed installation, the fan MUST be higher than the
enclosing structure

Increase airflow and maintenance clearances for side-enclosed or multiple
unit applications

Allow free space above the fans to prevent air recirculation

Ensure that there is a safe access and operating area provided for unit controls.

CAUTION

Prior to connecting services, ensure that the equipment is installed and
completely level.

Airflow & Maintenance
Clearances


A

A

B

C

D

Application

Distance from Overall Base Dimension (mm)

A

B

C

D

Free of walls and overhang

1300

1300

1300

1300

Enclosed to A

2600

1300

1300

1300

Unit parallel with A

2600

1300

1300

1300

Enclosed to B

1300

2600

1300

1300

Unit in line with B

1300

1300

1300

1300

Unit in line with C Controls End

1300

1300

2600

1300

Enclosed to C

1300

1300

2600

1300