Deltachill ™ chillers, Chillers, Electrical data regular quiet continued – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 68

Advertising
background image

DELTACHILL

Chillers

68

Chillers

Technical Manual : 7022932_V1.9_11/2013


Electrical Data Regular Quiet Continued

ELECTRICAL DATA

DCC019DR-04AFK0

DCC020DR-06AFK0

DCC021DR-04AKK0

Unit Data

Nominal Run Amps

(1)

A

130.7

139.3

149.3

Maximum Start Amps

(2)

A

343.2

411.8

331.3

Recommended Mains Fuse Size

A

160

160

160

Mains Supply

VAC

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

80

80

80

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

4

6

4

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15

15

15

Motor Rating

kW

2

2

2

Condenser Fan - Per Fan (EC)

Quantity

4

6

4

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Compressor - Per Compressor

Nominal Run Amps

A

33.0 / 47.5

33.0 / 47.5

33.0 / 33.0

Quantity

2 + 1

2 + 1

2 + 2

Motor Rating

kW

18.8 / 28.2

18.8 / 28.2

13.7 / 18.8

Sump Heater Rating

W

130 + 75

130 + 75

75

Start Amps (2)

A

215 / 260

215 / 320

215 / 215

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Circuit 1 Comp RLA (PFC)

28.5

28.5

28.5

Circuit 2 Comp RLA (PFC)

42.8

42.8

28.5

Nominal Run Amps

A

117.0

125.6

131.2

Maximum Start Amps

A

394.2

402.8

317.7

Compressor Nominal Run Amps

A

28.5 / 42.8

28.5 / 42.8

28.5 / 28.5

Recommended Mains Fuse Size

A

160

160

160

Electronic Soft-start

Nominal Run Amps

A

130.73

139.33

149.28

Maximum Start Amps

A

239.24

283.84

245.26

Recommended Mains Fuse

A

160

160

160

Power Factor Correction & Electronic Soft Start

Nominal Run Amps

A

117.0

125.6

131.2

Maximum Start Amps

A

266.2

274.8

231.7

Compressor Nominal Run Amps

A

28.5 / 42.8

28.5 / 42.8

28.5 / 28.5

Recommended Mains Fuse Size

A

160

160

160

Standard Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

5

5

6.2

Unit Nominal Run Amps

A

135.7

144.3

155.5

Recommended Mains Fuse Size

A

160

160

160

Motor Rating

kW

2.2

2.2

3

Larger Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

6.6

6.6

8.9

Unit Nominal Run Amps

A

137.3

145.9

158.2

Recommended Mains Fuse Size

A

160

160

160

Motor Rating

kW

3

3

4

Standard Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

4.5

4.5

6.3

Unit Nominal Run Amps

A

135.2

143.8

155.6

Recommended Mains Fuse Size

A

160

160

160

Motor Rating

kW

2.2

2.2

3

Larger Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

6.3

6.3

8

Unit Nominal Run Amps

A

137.0

145.6

157.3

Recommended Mains Fuse Size

A

160

160

160

Motor Rating

kW

3

3

4

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.

(2) Starting amps refers to the direct on line connections.