Chillers deltachill, Chillers, Electrical data extra quiet continued – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 83

Advertising
background image

Chillers

DELTACHILL

Chillers

83

Technical Manual :7022932_V1.9_11/2013

Electrical Data Extra Quiet Continued

ELECTRICAL DATA

DCC036DX-08BMS0

DCC038DX-10BMS0

DCC039DX-08BSS0

Unit Data

Nominal Run Amps

(1)

A

244.2

249.2

278.4

Maximum Start Amps

(2)

A

516.7

521.7

495.3

Recommended Mains Fuse Size

A

315

315

315

Mains Supply

VAC

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

100

100

100

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

8

10

8

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.27

1.27

1.27

Condenser Fan - Per Fan (EC)

Quantity

8

10

8

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Compressor - Per Compressor

Nominal Run Amps

A

43.1 / 47.5

43.1 / 47.5

43.1 / 43.1

Quantity

3 + 2

3 + 2

3 + 3

Motor Rating

kW

24.0 / 28.2

24.0 / 28.2

24.0 / 24.0

Sump Heater Rating

W

130 + 75

130 + 75

75

Start Amps (2)

A

260 / 320

260 / 320

260 / 260

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Circuit 1 Comp RLA (PFC)

36.5

36.5

36.5

Circuit 2 Comp RLA (PFC)

42.8

42.8

36.5

Nominal Run Amps

A

215.0

220.0

238.9

Maximum Start Amps

A

492.2

497.2

462.4

Compressor Nominal Run Amps

A

36.5 / 42.8

36.5 / 42.8

36.5 / 36.5

Recommended Mains Fuse Size

A

315

315

315

Electronic Soft-start

Nominal Run Amps

A

244.2

249.2

278.4

Maximum Start Amps

A

388.7

393.7

391.3

Recommended Mains Fuse

A

315

315

315

Power Factor Correction & Electronic Soft Start

Nominal Run Amps

A

215.0

220.0

238.9

Maximum Start Amps

A

364.2

369.2

358.4

Compressor Nominal Run Amps

A

36.5 / 42.8

36.5 / 42.8

36.5 / 36.5

Recommended Mains Fuse Size

A

315

315

315

Standard Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

8.9

8.9

12

Unit Nominal Run Amps

A

253.1

258.1

290.4

Recommended Mains Fuse Size

A

315

315

315

Motor Rating

kW

4

4

5.5

Larger Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

12

12

14

Unit Nominal Run Amps

A

256.2

261.2

292.4

Recommended Mains Fuse Size

A

315

315

315

Motor Rating

kW

5.5

5.5

7.5

Standard Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

11.2

11.2

11.2

Unit Nominal Run Amps

A

255.4

260.4

289.6

Recommended Mains Fuse Size

A

315

315

315

Motor Rating

kW

5.5

5.5

5.5

Larger Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

11.2

11.2

11.2

Unit Nominal Run Amps

A

255.4

260.4

289.6

Recommended Mains Fuse Size

A

315

315

315

Motor Rating

kW

5.5

5.5

5.5

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.

(2) Starting amps refers to the direct on line connections.