Electrical Data Free Cool Chiller Regular Quiet Continued
ELECTRICAL DATA
DCF039DR-10BMS0
DCF044DR-10BSS0
DCF014SX-04AL00
Unit Data
Nominal Run Amps
(1)
A
269.2
303.4
96.1
Maximum Start Amps
A
541.7
520.3
313.1
Recommended Mains Fuse Size
A
315
315
125
Mains Supply
VAC
400 V 3 PH 50 Hz
Max Mains Incoming Cable Size
mm²
Direct to Bus Bar
Recommended Permanent Fuse Size
A
16
16
16
Permanent Supply
VAC
230 V 1 PH 50 Hz
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Control Circuit
VAC
24V/230VAC
Evaporator
Pad Heater Rating
W
100
100
80
External Trace Heating
Available (fitted by others)
W
500
500
500
Condenser Fan - Per Fan (AC)
Quantity
10
10
4
Full Load Amps
A
4.3
4.3
2.5
Locked Rotor Amps
A
15
15
8.8
Motor Rating
kW
2
2
1.27
Condenser Fan - Per Fan (EC)
Quantity
10
10
4
Full Load Amps
A
3.9
3.9
3.9
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.56
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
47.5 / 43.1
43.1 / 43.1
43.1
Quantity
2 + 3
3 + 3
2
Motor Rating
kW
28.2 / 24.0
24.0 / 24.0
24.0
Sump Heater Rating
W
130 + 75
75
75
Start Amps
A
320 / 260
260 / 260
260
Type Of Start
Direct on line
OPTIONAL EXTRAS
Power Factor Correction
Circuit 1 Comp RLA (PFC)
42.8
36.5
36.5
Circuit 2 Comp RLA (PFC)
36.5
36.5
N/A
Nominal Run Amps
A
240.0
263.9
83.0
Maximum Start Amps
A
517.2
487.4
306.5
Compressor Nominal Run Amps
A
42.8 / 36.5
36.5 / 36.5
36.5
Recommended Mains Fuse Size
A
315
315
125
Electronic Soft-start
Nominal Run Amps
A
269.2
303.4
96.1
Maximum Start Amps
A
413.7
416.3
209.1
Recommended Mains Fuse
A
315.0
315.0
125.0
Power Factor Correction & Electronic Soft Start
Nominal Run Amps
A
240.0
263.9
83.0
Maximum Start Amps
A
389.2
383.4
202.5
Compressor Nominal Run Amps
A
42.8 / 36.5
36.5 / 36.5
36.5
Recommended Mains Fuse Size
A
315
315
125
Condenser Fan - Per Fan (EC Extra Freecooling)
Quantity
10
10
N/A
Full Load Amps
A
4.5
4.5
N/A
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.86
2.86
N/A
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
14
14
6.6
Unit Nominal Run Amps
A
283.2
317.4
102.7
Recommended Mains Fuse Size
A
315
355
125
Motor Rating
kW
7.5
7.5
3
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
20.8
20.8
9.8
Unit Nominal Run Amps
A
290.0
324.2
105.9
Recommended Mains Fuse Size
A
315
355
125
Motor Rating
kW
11
11
4
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
14.8
14.8
6.3
Unit Nominal Run Amps
A
284.0
318.2
102.4
Recommended Mains Fuse Size
A
315
355
125
Motor Rating
kW
7.5
7.5
3
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
21.2
21.2
8
Unit Nominal Run Amps
A
290.4
324.6
104.1
Recommended Mains Fuse Size
A
315
355
125
Motor Rating
kW
11
11
4
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.