Power connections, Standard, Power connections 12 – Badger Meter B3000 User Manual

Page 12: Standard 12, Caution

Advertising
background image

Compact Digital Flow Monitor, Model B3000

Page 12

March 2014

POWER CONNECTIONS

Standard

The power supply used in the B30A/B/X/Z is an internal lithium 3 6V DC “D” cell that will power the monitor for about six years

when no outputs are used The monitor can also get power from a 4-20 mA current loop (see

Figure 9

and

Figure 10

) If the

current loop is used a sensing circuit within the monitor detects the presence of the current loop and disconnects the battery

from the circuit The B30L/M/W/ versions use loop power only and the B30S uses solar power only

JP1

JP2

JP3

Input

Total P

ulse

Sig
nal

P1

Freq. In

4-20mA

Iso Total Pluse

TR_B

TR_A

RS485 Gnd

Setpoint 1

Setpoint 2

Gnd

+

+

+

Total Reset

OC Total Pluse

Signal Gnd

TB1

Mag

Pulse

Iso

OC

Low

High

4-20 mA

Current Loop

(10…28V DC)

Load

10…28V DC

Freq. In

4-20mA

Iso Total Pluse

+

+

+

Total Reset

OC Total Pluse

Signal Gnd

TR_B

TR_A

RS485 Gnd

Setpoint 1

Setpoint 2

Gnd

+

P2

3.6Vdc

Battery

JP3

Total Pulse

ISO

OC

JP1

Input

Mag

Pulse

JP2

TB2

TB1

P1

Signal

Low

High

P1

4-20 mA

Current Loop

(10…28V DC)

Load

10…28 VDC

Figure 9: Loop power connections (NEMA 4X)

Figure 10: Loop power connections (Ex-Proof)

CAUTION

GROUNDING FOR THE EXPLOSION PROOF ENCLOSURE IS NECESSARY. THE EXPLOSION PROOF ENCLOSURE IS

PROVIDED WITH A GROUNDING SCREW ON THE INSIDE OF THE ENCLOSURE. THE CONDUCTOR USED FOR GROUNDING

MUST BE OF A WIRE GAGE EQUAL TO OR GREATER THAN THE SIGNAL WIRES BEING USED. SEE

FIGURE 11

.

The explosion proof enclosure is provided with a grounding screw on the inside of the enclosure The conductor used for

grounding must be of a wire gage equal to or greater than the signal wires being used

To Earth Ground

Figure 11: Required grounding for Ex-proof enclosure