Badger Meter B3000 User Manual

Page 27

Advertising
background image

Programming Manual

Page 27

March 2014

Minimum

Flow

Maximum

Flow

Output ON

OFF S

etpoin

t

ON S

etpoin

t

Hysteresis

Output OFF

Figure 26: Set point actions

OTE:

N

Neither the set point nor the hysteresis values are checked against the meter size to see if they are appropriate Care

should be used when entering these values, especially in critical applications, as it is possible to enter inappropriate

values preventing the outputs from working as expected

Trip SP 1 TripSP1
Extended Function
The trip parameter can be set for either High or Lo When set to high the open collector transistor stops conducting and

sends the output high when the set point is reached The output will not go low again until the flow rate falls below the

set point minus the hysteresis value Similarly when set to low the, open collector transistor starts conducting sending the

output low when the set point is reached The output will not go high again until the flow rate exceeds the set point plus the

hysteresis value
For example if the set point is set to ten gpm, the hysteresis is set to two gpm and the trip set point is set to high (see

Figure

27

) When the flow goes above ten gpm the OC transistor stops conducting and the output goes high The output stays high

until the flow rate drops below eight gpm which is the set point (ten gpm) minus the hysteresis (two gpm)

Minimum

Flow

Maximum

Flow

Output ON

OFF (8 g

pm)

Setpoin

t (10 g

pm)

Hysteresis

(2 gpm)

Output OFF

Figure 27: Set point example

At the TripSP1 prompt, press ENTER The tripping condition setting is displayed If the current setting is correct, press ENTER

to advance to the next parameter
If the current setting requires a change, press

► to advance to the alternate choice Once the correct choice is displayed, press

ENTER to save the new trip condition and advance to the next parameter

Advertising