Figure 24 – Badger Meter B3000 User Manual

Page 26

Advertising
background image

Compact Digital Flow Monitor, Model B3000

Page 26

March 2014

Set Point 1 SetPt 1
Extended Function
The set point is the flow value at which the output transistor changes state It is set using the same units as the rate units

are entered

JP1

JP2

JP3

Input

Total P

ulse

Sig
nal

P1

Freq. In

4-20mA

Iso Total Pluse

TR_B

TR_A

RS485 Gnd

Setpoint 1

Setpoint 2

Gnd

+

+

+

Total Reset

OC Total Pluse

Signal Gnd

TB1

Mag

Pulse

Iso

OC

Low

High

Open Collector

Control Output

1 and 2

2.2…10K

Pull-up

Resistor

V

CC

Internal

100 mA

Maximum

TR_B

TR_A

RS485 Gnd

Setpoint 1

Setpoint 2

Gnd

+

P2

3.6Vdc

Battery

TB1

P1

P1

Internal

Open Collector

Control Output

1 and 2

2.2…10K

Pull-up

Resistor

V

CC

100 mA

Maximum

Figure 24: Set point output (NEMA 4X)

Figure 25: Set point output (Ex-Proof))

At the SetPt 1 prompt, press ENTER The most significant digit of the current setting begins to flash If the current setting is

correct, press ENTER to advance to the next parameter
If the current setting requires a change, press

► to advance to the first digit of the required set point value Once the correct

place is reached use

▲ to increment the digit until it matches the first number of the required set point Use ► to advance to

the next digit of the required set point value then use

▲to increment the display digit until it matches the next digit of the

required set point Repeat this step for the all the digits of the set point and then press ENTER to save the new set point and

advance to the next parameter
Hysteresis 1 HystSP1
Extended Function
Hysteresis is used to modify how the output transistor reacts around a set point by taking recent history into account

Hysteresis prevents an output from turning on and off rapidly when the programed flow rate is at or very near the set point
For example, a low flow alarm is set to activate when the flow falls below a pre programed point When the flow is reduced to

the set point, even minute changes of flow above the set point turns the output off disabling the alarm Without hysteresis, if

the flow rate fluctuates slightly above and below the set point the output rapidly cycle between on and off states
Another example is a thermostat controlling a heater The thermostat turns the heater on when the temperature drops below

“A” degrees, but won’t turn it off until the temperature rises above “B” degrees The temperature between “A” and “B” is know as

the hysteresis Thus the on/off output of the thermostat to the heater when the temperature is between “A” and “B” depends

on the “history” of the temperature This prevents rapid switching on and off as the temperature drifts around the set point
Refer to the graphical representation of the hysteresis setting as shown in

Figure 26

. The hysteresis value is set using the same

units as the rate units are entered
At the HystSP1 prompt, press ENTER The most significant digit of the current setting begins to flash If the current setting is

correct, press ENTER to advance to the next parameter
If the current setting requires a change, press

► to advance to the first digit of the required hysteresis value Once the correct

place is reached use

▲ to increment the digit until it matches the first number of the required hysteresis Use ► to advance

to the next digit of the required hysteresis value then use

▲ to increment the display digit until it matches the next digit of

the required hysteresis Repeat this step for the all the digits of the hysteresis and then press ENTER to save the new hysteresis

and advance to the next parameter

Advertising