Compact Digital Flow Monitor, Model B3000

Page 8

March 2014

Status Alarms

B30B/L/S/W/X

None

Modbus Digital Communications

B30A/M/Y/Z

Modbus RTU over RS485, 127 addressable units / 2-wire network, 9600 baud, long integer and

single precision IEEE754 formats; retrieve: flow rate, job totalizer, grand totalizer, alarm status and

battery level; write: reset job totalizer, reset grand totalizer

B30B/L/S/W/X

None

Data Configuration and Protection

B30A/B/L/M/W/X/

Y/Z

Two four-digit user selectable passwords; level one password enables job total reset only, level two

password enables all configuration and totalizer reset functions

OTE:

N

Not applicable on solar powered units

Totalizer Operation

Common Functions

Monitors contain two totalizers: Job and Grand The user can enable or disable the grand totalizer

function If grand totalizer is enabled, it shares the seven-digit display line with the job totalizer –

alternating between job and grand Grand totalizer rollovers are displayed with a count value that

increments at each rollover Totalizers are automatically backed up into non-volatile FLASH memory

every twenty minutes and prior to battery expiration; manually via keypad or when signaled via

Modbus (B30A/M/Y/Z only)

Totalizer Reset

B30A/B/L/M/S only: The job totalizer can be reset by momentarily contacting the total reset

terminal to ground or pressing MENU and ENTER simultaneously The grand totalizer can be reset

via selection in the advanced menu or modbus

OTE:

N

Modbus not applicable on solar powered units

B30W/X/Y/Z: *The job totalizer can be reset via the “through the glass” touch sensor, by

momentarily contacting the total reset terminal to ground or pressing MENU and ENTER

simultaneously The grand totalizer can be reset via selection in the advanced menu or Modbus

command

Totalizer Preset

User can preset job total values

Certifications

Safety

B30A/B/L/M/S: Class I Division 1, Groups C, D; Class II, Division 1 Groups E, F, G; Class III for US and

Canada Complies with UL 913 and CSA C22 2 No 153
B30W/X/Y/Z: Class I Division 1 Groups B, C, D; Class II, Division 1, Groups E, F, G; Class III for US and

Canada Complies with UL 1203 and CSA C22 2 No 30
ATEX II 2 G Ex d IIC T4 Gb and ATEX II D Ex tb IIIC T125 °C Db
Complies with Directive 94/9/EC

Entity Parameters

B30A/B/L/M only

4-20 mA Loop: Vmax = 28V DC Imax = 26 mA

Ci = 0 5 μF Li = 0 mH

B30A/B/L/M/S only

Pulse Output: Vmax = 28V DC

Imax = 100 mA Ci = 0 μF

Li = 0 mH

B30A/B/L/M/S only

Reset Input: Vmax = 5V DC

Imax = 5 mA

Ci = 0 μF

Li = 0 mH

B30A/M only

RS485: Vmax = 10V DC

Imax = 60 mA

Ci = 0 μF

Li = 0 mH

B30A/B/L/M/S only

Turbine Input: Voc = 2 5V

Isc = 1 8 mA

Ca = 1 5 μF La = 1 65 H

EMC

2004/108/EC

Measurement Accuracy

Common Accuracy 0 05%