Flow at 20 mA Fl=20mA
Basic Function
When the display is operated using loop power, the flow rate that corresponds to 20 mA must be set This setting normally

represents the maximum rate of the flow sensor connected to the display but other entries are possible
At the Fl=20mA prompt, press ENTER The current setting will begin to flash If the current setting is correct, press ENTER to

advance to the next parameter If the current setting requires a change, use

▲ to increment the display digit until it matches

the first digit of the required maximum flow value Next press

► to advance to the next digit and using ▲ to increment the

second display digit until it matches the second digit of the

required value Repeat this step until the maximum flow at 20

mA is entered Press ENTER to save the new flow value
4-20 mA Calibration 4-20Cal
Extended Function
This menu item allows the fine adjustment of the Digital to

Analog Converter (DAC) that controls 4-20 mA output The

4-20 mA output is calibrated at the factory and under most

circumstances does not need to be adjusted If the output needs

to be adjusted for any reason the 4-20 mA calibration procedure

is used
The DAC used in the B3000 is an twelve bit device so the valid

entries range from 0…4095
4 mA Adjustment 4mA Out
To set the 4 mA value, connect an ammeter in series with the loop

power supply as shown in

Figure 23

At the 4-20Cal prompt, press ENTER

The display will now show a steady NO indication Press

▲ to change to

a YES display and press ENTER The 4 mA DAC setting is typically between

35…50 Using

▲ and ► while monitoring the ammeter, adjust the 4 mA value

to obtain a 4 mA reading on the ammeter The

▲ increases the DAC value

and ► decreases the DAC value. When a steady 4 mA reading is obtained on

the ammeter, press ENTER to lock in this value and move to the 20 mA adjustment

Figure 23: 4-20 mA calibration setup

20 mA Adjustment 20mAOut
The 20 mA adjustment is performed using the same procedure as the 4 mA adjustment While monitoring the ammeter,

adjust the 20 mA DAC value to obtain a 20 mA reading The

▲ increases the DAC value and ► decreases the DAC value.

When a steady 20 mA reading is obtained on the ammeter, press ENTER to lock in this value and move to the next parameter
4-20 mA Test 4-20Tst
The B3000 monitor contains a diagnostic routine that allows the simulation of mA output values between 4…20 to check

output tracking At the 4-20 TEST prompt the current is shown as a flashing number Use

▲ to increase the simulated mA

output in increments of 1 mA The

► decreases the mA output. The ammeter should track the simulated mA output If a

4-20 mA test is not necessary, press ENTER to move to the next parameter

OTE:

N

Pressing ENTER when the monitor is in test mode will exit the test mode and move on to the next

programming parameter

P1

Freq. In

4-20mA

Iso Total Pluse

TR_B

TR_A

RS485 Gnd

Setpoint 1

Setpoint 2

Gnd

+

Total Reset

OC Total Pluse

Signal Gnd

TB1

Mag

Pulse

Iso

OC

Low

High

+

+

Input

Total P

ulse

Sig
nal

JP1

JP2

JP3

4-20 mA

Current Loop

(11 to 30 VDC)

POWER

SUPPLY

10A MAX

FUSED

400mA

FUSED

CAT III

1000V

HOLD

MIN MAX

REL

Hz % ms

RANGE

AutoHOLD FAST MIN MX

LOGGING

YES

CANCEL

SAVE

NO

SETUP

µA

mA

A

W

V

TEMPERATURE

COM

OFF

nS

W

VIEW MEM

CLEAR MEM

V

dB

mV

dB

ac+dc

V

ac+dc

A

mA

mV

ac+dc

mA

A

µA

ac+dc

µA

°C

°F

MEM

HM

MS

51000

AUTO MANUAL

%

FA S T M A X M I N AV G

0

0

LOG

HOLD

Advertising