Communication Menu

CommunicationE: Port Settings

Interfaces

Modbus RTU

RS-232, RS-485 and RS-422 with Modbus RTU .

Connector

Label

RS Interfaces

422

232

485

A

A

RxD

B

B

Z

Z

TxD

B

Y

Y

A

G

G (GND)

See

Figure 23 on page 17

for wiring

diagram .

Mode can be configured by DIP switches also if Termination is ON or OFF .

M-Bus

For future release .

HART

For future release .

Modbus

Address

This parameter configures the Modbus address in the range from 1…247 .

RS-232,

RS-422,

RS-485

Baudrate: 1200, 2400, 4800, 9600, 19200, 38400 Bd
Parity: Even, Odd, Mark

M-Bus

Address

For future release .

Ethernet

IP Address

For future release .

IP Mask
IP Gateway
MAC Address

ADE

Control

On or Off

Protocol

1 standard messages

2 extended messages

Dial

4 to 9

Resolution

0 .001 / 0 .01 / 0 .1 / 1 / 10 / 100 / 1000 / 10,000

M1000 main menu programming options