Manual local and remote settings, Software supported configurations, Failure handling – Badger Meter SRD/SRI Valve Positioners User Manual

Page 10

Advertising
background image

Manual Local and Remote Settings

Actuator mode

linear or rotary actuator

Linear valve

left or right mounted

Rotary actuator

opening clockwise or counter-

clockwise

Characteristic of

setpoint

linear, equal percentage, invers-equal

percentage or custom (22 points)

Valve function

opens or closes with increasing

setpoint

Split range

free upper and lower values

Travel limits

free upper and lower values

Cutoffs

free upper and lower values

Stroke range

configurable

Temperature unit

configurable (°C or °F)

Autostart

- Endpoints
- Standard Autostart
- Enhanced Autostart
- Smooth response
- Fast response

Control

parameters

Determined during Autostart

Working range

Freely adjustable (for indication on

LCD

Manual

adjustment of

P-gain, I-time, T63-time and dead

band

Manual operation Manual input of setpoint to drive the

valve in steps of 12 5 % or 1 %

Pneumatic test

Function to test the pneumatic

output

Workshop

input and angle calibation

LCD language

dependent on version

LCD orientation

dependent on version

PROFIBUS-PA

Bus address

FOUNDATION

Fieldbus

Simulation, Switch from Link Master

to Basic Field Device

Software Supported Configurations

• By means of Hand Held Terminal (HART)
• PC by means of VALcare Software
• PC among others by means of PC20/ PC50 /IFDC
• I/A Series System and other DCSs
• Depending on the version, configurations can be

achieved by a non-contact, protocol-independent

infrared interface by means of IRCOM

Failure Handling

In case

of Single

Acting,

Safety

position at

Air supply failure

pressure y1 = zero

Electric power

failure

pressure y1 = zero

Failure of

electronics

pressure y1 = zero

In case of

Double

Acting or

spool valve

amplifier,

safety

position at

Air supply failure

pressure y1 = zero /

y2 = zero

Electric power

failure

pressure y1 = zero /

y2 = full air supply

pressure

Failure of

electronics

pressure y1 = zero /

y2 = full air supply

pressure

For all types

of amplifiers

(with FF H1

or Profibus

PA)

Failure of communication is recognized

by configurable watch dog with response

delay of 0 1 s to 24 h

Behavior

configurable as

pressure y1 = zero or

stop at last value or a

configured value

Diagnostic

report

via communication and local LCD

Historical

status

is set if alarm was activated at any time

(also just short alarms)
Reset

by acknowledging

Spool Valve Amplifier for Single and Double Acting

Application
Spool valve amplifier as option for the SRD991 can be

used with double acting actuator and also with single

acting actuator
In case of single acting application, one of the pneumatic

output must be closed:
• If y1 is used, y2 is closed and failure handling for Electric

power failure and Failure of electronics becomes y1=zero

• If y2 is used, y1 is closed and failure handling for Electric

power failure and Failure of electronics becomes y2=full

air supply

Functional Specifications

Page 10

August 2014

POS-UM-00223-EN-02