Badger Meter SRD/SRI Valve Positioners User Manual

Page 21

Advertising
background image

Position Feedback 4…20 mA and Alarm

Code F with Electrical Classification ATEX
Code Q with Electrical Classification FM/CSA
• Stroke / angle derived from positioner feedback
• 1 output analog, galvanically separated, two-wire system

according to DIN 19234, for external supply

• 0 % and 100 % configurable

Supply Voltage

8…36V DC

1) 2)

Signal Range

3 8…20 5 mA

Device Fault

< 50 μA

Terminals for AI1

C: 31+ D: 32–

Feedback Signal

Can be reversed (20 --> 4 mA)

One binary alarm output, galvanically separated, two-wire

system, according to DIN 19234, for external supply

Supply Voltage

External, 8…36V DC

1) 2)

Logic

No alarm < 1mA
Alarm >3 mA
Device fault < 50 μA

Configurable as switch output:

Limit Value Not

Exceeded

< 50 μA

Limit Value

Exceeded

> 20 mA/20 V / > 40 mA/10 V

(power derated)

Terminals for AB1

3)

A: 81+ B: 82–

1) Other values in hazardous areas

2) On request we can specify higher voltage limits

3) Terminals 81 and 82 are marked as Terminals 21 and 22 in certificate of conformity

The binary output for Alarm will be activated in the

following cases:
• Remaining control deviation
• Circuit to I/P module is disturbed
• Circuit to potentiometer is disturbed
• Calibration error:

◊ No angle calibration
◊ No current calibration
◊ Autostart failed

These pre-settings can be configured via communication

with the Alarm Link function in the DTM

One module “Additional inputs / outputs” 8 can be plugged

onto main electronics 40:

• 2 binary inputs or
• 2 binary outputs or
• 2 binary in/outputs or
• Position feedback and alarm
DTM Configuration Window

Electrical Classification ATEX
• For types of protection and temperature classes as basic

device, see

page 13

• Additions for this option, Type AI 638 Q, in EC – Certificate

of Conformity PTB 00 ATEX 2128:

◊ For use in hazardous areas in circuits certified

as intrinsically safe with the maximum values

as described in the Certificate of Conformity, 5

Supplement

◊ The electric circuits of Position Feedback 4…20 mA

are galvanically separated from all other circuits and

from earth

Additional Equipment

Page 21

August 2014

POS-UM-00223-EN-02

Advertising