Input for Remote Potentiometer – Code D
This option is necessary when the positioner is not mounted

directly onto the valve but far away of it In this case a

potentiometer with 3 wires must be mounted onto the valve

to give the valve position to the controller
Remote potentiometer type to use in connection to this

option: Resistance of 5 kOhm up to 10 kOhm (for other value

of resistance please consult us)
If the following requirements are observed, the set-up

is insensitive to electrical disturbances caused by high

electromagnetic fields, EMC and HF-radiation
• Cable length max is 10 m (32 ft)
• Cable specification (not supplied):

◊ 3-wire twisted pair, shielded
◊ Shield needs to be connected on both ends to the

internal ground

◊ Shield endings need to be kept very short when

connecting to the ground

◊ An HF cable gland is not required

For more information about remote mounting,

see TI EVE0105_R