Srd991 without communication srd991-xdxxxx, Srd991-xdxxxx 15 – Badger Meter SRD/SRI Valve Positioners User Manual

Page 15

Advertising
background image

SRD991 with Communication PROFIBUS-PA and

FOUNDATION Fieldbus H1

SRD991-xPxxxx or SRD991-xQxxxx

PROFIBUS-PA

Data Transfer

According to PROFIBUS- PA profile class B

based on EN 50170 and DIN 19245 part 4

GSD File

The actual file can be downloaded from

our homepage

Configuration

Local / Display See

page 9

Software

VALcare DTM

Hardware

PC- or PCMCIA- interfaces from Softing

I/A Series

System

FBM 223 in combination with CP60

Other Control

Systems

All Profibus-PA- compatible, e g Siemens

SIMATIC PDM (Process Device Manager)

FOUNDATION Fieldbus H1

Data Transfer

FF Specification Rev 1 4, Link-Master (LAS)

Certified

According To

ITK 4 01

Function

Blocks

PID, AO, Transducer, Resource

Certified

According To

ITK 4 6

Function

Blocks

PID, AO, 2xDI, 1xDO Transducer, Resource

Additional

Functionality

Flat Addressing

DD Files

The actual file can be downloaded from

our homepage

Configuration

Local / Display See

page 9

Software

VALcare DTM or National Instruments NI-

FBUS configurator

Hardware

FBUS-interfaces from National

Instruments (AT-FBUS and PCMCIA- FBUS)

I/A Series

System

FBM220 or FBM221 in combination with

CP60

Other Control

Systems

All FOUNDATION Fieldbus H1- compatible,

e g SMAR, Fisher Rosemount Delta-V,

Honeywell, Yokogawa, ABB

For both fieldbus devices

Input Signal

Digital

Supply

Voltage

9…32V DC

1)

Max. Supply

Voltage

48V DC

Operating

Current

10 5 mA ± 0 5 mA (base current)

Current

Amplitude

± 8 mA

Fault Current

Base current + 0 mA (base current + 4

mA by means of independent FDE-safety

circuit) according to IEC 1158-2

Operating

Values

According to IEC 1158-2

Startup Time

(Init Phase)

Approx 2 sec

Bus

Connection

Fieldbus interface based on IEC 1158-2

according to FISCO-Model

Power Supply Power supply is achieved dependant

on the application by means of fieldbus

power supply units or segment coupler

Electrical

Classification

See

page 13

1) Data of ”Intrinsically Safe” version

SRD991 without Communication

SRD991-xDxxxx

Signal Input

Two wire system

Reverse Polarity Protection Standard feature
Signal Range

4…20 mA

Operating Range

3 6…21 5 mA

Input Voltage

8 5…36V DC

1)

(unloaded)

Load

00 Ohms, 6 V at 20 mA

With applications without communication the capacity

parallel to input may not be higher than 100 μF
Startup Time

Approx 3 sec

Interruption Time Without

Power Down

With LCD, typ 80 ms

2)

1) On request we can specify higher voltage limits

2) Worst case conditions 4-20 mA, with position feedback option, i/p-output with max

current

Configuration

Local / Display

See

page 9

Software

VALcare (DTM)

Hardware

per modem EDC82

Electrical classification

See

page 13

Safety Requirements

Page 15

August 2014

POS-UM-00223-EN-02