Entry for remote potentiometer – code d, Entry for remote potentiometer – code d 22 – Badger Meter SRD/SRI Valve Positioners User Manual

Page 22

Advertising
background image

Entry for Remote Potentiometer – Code D

For remote mounting main unit
This remote application is used in applications where high

temperatures or vibration are present and can result in

negative influences to the control It can also be used in

places not easy to reach, to ensure an easier handling of the

unit, or for cylinders with large strokes
The Positioner SRD991 (Remote Unit) is mounted far away

from the valve or cylinder in a safe environment
The Potentiometer unit is mounted on the valve or cylinder

This potentiometer unit can be made of a derivative version

of the SRI990 positioner (only potentiometer in the housing)

or of an external potentiometer like a linear potentiometer

for application onto cylinders, for example
This option is to be used with a potentiometer unit 3-wire

system with ca 5 kOhm resistance
If the following requirements are observed, the setup

is insensitive to electrical disturbances caused by high

electromagnetic fields, EMC and HF-radiation
• Cable Length max is 10 m (32 ft)
• Cable Specification (not supplied):

◊ 3-wire twisted pair, shielded
◊ Shield needs to be connected on both ends to the

internal ground

◊ Shield endings need to be kept very short when

connecting to the ground

◊ An HF cable gland is not required

For more information about remote mounting please consult

TI EVE0105_R