Operation and Configuration

The local LCD enables a fast and easy configuration as well as

univocal diagnostic
• Local – with local key pads
• Display – Multi-lingual Graphic LCD, some versions with

5 LEDs

The positioner in the version with LCD contains three

different menu languages Standard menu languages are

English and German
Freely selectable third languages include French, Portugues,

Spanish, Italian, Swedish For the complete list, see

“Model Codes SRD991” on page 27

The third menu language has to be selected and specified

with the order, otherwise the standard is French
The third, freely selectable menu language can be modified

to another language by means of the VALcare DTM

2

The

additional languages can be downloaded from the PLF

selector on our website

Diagnostics

In the field:
• Status and Diagnostic messages via LCD
• Via VALcare or Valve Monitor DTM

4

• Service Management for planning and scheduling of

service intervals

• Histograms for displaying the position- and response-

history over time

• Partial Stroke Test for the functional inspection of safety

related actuators

• Hours in operation, cycle counter and travel sum of the

actuator are determined

• Surveillance of loop current
• Shows condition of device:

◊ Potentiometer
◊ IP Motor
◊ Exceeding range of actuator (possible indication for

wear of plug or seat)

◊ Remaining control deviation (possible indication

for jammed actuator, blocked valve stem or

plug, insufficient air capacity, supply air pressure,

positioning pressure)

If equipped with optional pressure sensors:
• Monitoring of the stem friction
• Histograms for displaying the friction-history over time

• Surveillance of air supply and output pressure, each with

display of physical value

Additional diagnostical possibilities in control operation by

means of optional external sensors

Service Plug and IrCom

All basic devices are equipped with a service plug "A" at the

front side There, via RS232 interface, a PC with VALcare (DTM)

can be connected via modem EDC82 (galv separa- ted,

not Ex)

If the SRD is equipped with option “IrCom” B , communication

can take place contactless via infrared with the positioner

(even with a closed cover!) A modem “IR Interface” (not Ex)

connected via RS232 interface to a PC with VALcare (DTM)

makes communcation possible up a range of approximately

0 5 m
(If the notebook has an IrDa interface, this cannot be used

despite being similar technology as IrDa instruction set has

no communication commands for positioners )

2) With the versions “Intelligent without communication” this is only possible with

modem EDC82

3) By means of “Additional inputs / outputs”

4) For the SRD991 without communication the use of the service plug is necessary to

have access at the diagnostic with DTM

Functional Specifications

Page 9

August 2014

POS-UM-00223-EN-02