Badger Meter SRD/SRI Valve Positioners User Manual

Page 19

Advertising
background image

Two Binary Outputs (Limit Signals) – Code P

• Stroke / angle derived from positioner feedback
• 2 galvanically separated limit signals
• Signaling of limit value exceeding of the measured valve

stem position

• Limit signals / alarms freely configurable via local keys or

via communication

• Two-wire system, according to DIN 19234, for

external supply

Supply Voltage

8…36V DC

1) 2)

Logic

limit value not

exceeded

< 1 mA

limit value

exceeded

> 2 2 mA (typ 6 mA)

device fault

< 50 μA

Configurable as

Switch Output

limit value not

exceeded

< 50 μA

limit value

exceeded

> 20 mA/20 V / > 40

mA/10 V

(power derated)

Reference

AB1 for upper, AB2 for lower limit

Terminals for AB1

3)

A: 81+ B: 82–

Terminals for AB2

3)

C: 83+ D: 84–

1) Other values in hazardous areas

2) On request we can specify higher voltage limits

3) Terminals 81…84 are marked as K21…K32 within certificate of conformity

Electrical Classification ATEX
• Types of protection and temperature classes as basic

device, see

page 13

• Additions for this option, Type AI 638 P, in EC- Certificate

of Conformity PTB00ATEX2128:
◊ For use in hazardous areas in circuits certified as

intrinsically safe with the following maximum values:

Ui= 16 V, Ii= 80 mA, Pi= 250 mW

◊ Internal capacitance and inductance: Ci= 26 nF,

Li= 5 μH The electric circuits of 2 Binary Outputs are

galvanically separated from all other circuits and

from earth

One module “Additional inputs / outputs” 8 can be plugged

onto main electronics 40:

• 2 binary inputs or
• 2 binary outputs or
• 2 binary in/outputs or
• Position feedback and alarm
DTM Configuration Window

Additional Equipment

Page 19

August 2014

POS-UM-00223-EN-02