Badger Meter SRD/SRI Valve Positioners User Manual

Page 6

Advertising
background image

Premium Diagnostics

Advanced Diagnostics

Autostart

Yes

Yes

Custom Characterization

Yes

Yes

Autodiagnostic

Yes

Yes

Alarm Management

Yes

Yes

Alarm Output for Switching (with

Optionboard)

Yes

Yes

Status List acc. NE107

Yes

Yes

Position History

Yes

Yes

Response History

Yes

Yes

On Line Friction

Yes

Stepping Signature

Yes

Ramping Signature

Yes

Sensitivity Signature

Yes

Valve Signature

Yes

PST (Partial Stroke Test)

Yes

PST Predictive Maintenance

Yes

Additional equipment, built into the basic device:

Option Board 2 Binary Inputs or

B

2 external switches (supplied by SRD) release a control function in the SRD, e g

close valve (configurable)

Option Board 2 Binary Outputs or

P

2 binary outputs (to be supplied externally) become active during value limit in

excess of the measured valve position

Option Board 2 Binary Inputs/

Outputs or

E

2 channels, each configurable as an input or output (to be supplied externally)

Option Board Position Feedback

F,

Q

1 output 4…20 mA (to be supplied externally) gives stroke / angle of rotation,1

alarm output becomes active with a configurable event

Limit switch

T,

U,

R,

V

Supplies NAMUR signals when exceeding or falling below of two limit values

Inductive sensors, independent of the controller, in normal or safety version or

three-wire, or micro switches

D

Entry for remote potentiometer of external potentiometer unit

Pressure sensors

2 sensors measure the pressure of supply air and output y1 for Premium Diagnostics;

the values are passed on via communication

LCD or

Full text graphic LCD in 3 languages

LCD and IrCom

Full text graphic LCD in 3 languages and infrared interface

For accessories like manifolds and boosters, see

“Model Code Accessories” on page 29

Description

Page 6

August 2014

POS-UM-00223-EN-02