Srd991 with hart communication (srd991-xhxxxx), Srd991 with hart communication, Srd991-xhxxxx) 14 – Badger Meter SRD/SRI Valve Positioners User Manual

Page 14

Advertising
background image

1) With appropriate order only

2) National requirements must be observed

SRD991 with HART Communication

(SRD991-xHxxxx)

Signal Input

Two wire system

Reverse Polarity

Protection

Standard feature

Signal Range

4…20 mA

Operating Range

3 6…21 5 mA

Input Voltage

12…36 V DC

1)

(unloaded)

Load

420 Ohms, 8 4 V at 20 mA

Communication Signal

HART, 1200 Baud, FSK

(Frequency Shift Key)

modulated on 4…20 mA 0 5

Vpp at 1 kOhm load

Input impedance Zi

Z = 320 Ohms for AV voltage

0 5…10 kHz with < 3 dB

non-linearity

Cable Capacity and

Inductance

See HART standard

specifications (C < 100 nF)

Impedance of other devices at the input (parallel or serial)

must be within HART spec
Applications without communication require not to exceed

input capacitance parallel to the input not higher than

100 μF
Startup Time

Approx 3 sec

Interruption Time Without

Power Down

With LCD: typ 80 ms

2)

1) On request we can specify higher voltage limits

2) Worst case conditions 4-20 mA, with position feedback option, i/p-output with max

current

3) Check CP for suitable ECBs

Configuration

Local / Display

See

page 9

Software/Driver

VALcare or Valve

Monitor(DTM)

Hardware

HART Modem for RS232 or

USB port

Handheld Terminal

ex: HT991, HT375, HHT50

I/A Series System

FBM215 or FBM218

(redundant) in combination

with CP60 3)/ FCP270

Other Control Systems

AMS, Siemens SIMATIC PDM

(ProcessDeviceManager),

Any decentralised Control

System

DTM for HART

Local Configuration

LCD Display, see

page 9

Trough HART Communication
• PC20 standalone Software for PC (only via RS232)
• VALcare
• Valve Monitor
• Can be integrated onto any FDT Frame onto any Host

suppending of FDT Frame

• H275/375
• AMS for Emerson
• PDM
• via service port

Safety Requirements

Page 14

August 2014

POS-UM-00223-EN-02