Additional Inputs / Outputs

Two Binary (Contact) Inputs – Code B
Two independent binary inputs, supplied with the basic

device, for connection of external switches
A connected switch is loaded with 3 5 V, 150 μA
The Binary Inputs option can also be used to activate PST

(Partial Stroke Test)
The binary inputs can be used for diagnostics or are also

configurable for the control functions:

Switch 1

Switch 2

Actuator Control Function

close

close

normal operation

open

close

go to stop at 0%

close

open

go to stop at 100%

open

open

hold last position

Terminals for:
• EB1—A: 13+ B: 14–
• EB2—C: 15+ D: 16–
For further information about the contact inputs please

consult TI EVE0105_B
Electrical Classification ATEX
• Types of protection and temperature classes of basic

device, see

page 13

• Additions for this option, Type AI 638 B, in EC- Certificate

of Conformity PTB 00 ATEX 2128:
◊ To this electric circuit only passive electric circuits

galvanically separated from earth may be attached

◊ The electric circuit has the following maximum

values: Uo= 7 88 V, Io= 11 4 mA, Po= 23 mW

• Characteristic is linear
For the maximum values of outer inductances and

capa- cities Lo and Co refer to the following table (Li and

Ci included):

IC

IIB

Lo [mH]

Co [μF]

Lo [mH]

Co [μF]

100

0 72

100

3 9

10

1 1

10

5 5

1

1 6

1

8 7

0 1

2 7

0 1

15

0 01

4 7

0 01

27

The electric circuits of 2 Binary Inputs are galvanically

connected with all other circuits but separated from earth
One module “Additional inputs / outputs” 8 can be plugged

onto main electronics 40:

• 2 binary inputs or
• 2 binary outputs or
• 2 binary in/outputs or
• Position feedback and alarm
DTM Configuration Window