4 example without safe shut-down method, Example without safe shut-down method – NORD Drivesystems BU0530 User Manual

Page 27

Advertising
background image

2 Description of function

BU 0530 GB-3712

27

2.3.4

Example without safe shut-down method

It is possible to implement the safety functions STO or SS1 with a digital input and a protective switching
device. With this switching version, as a maximum, Safety Category 1 as per DIN EN ISO 13849-1 can be
achieved, if in addition to the digital inputs, all other components (protective switching device, emergency stop
button, wiring) fulfil the requirements for Category 1.
This switching version should only be considered if only low requirements for functional safety need to be
fulfilled and if the risk assessment has shown that failure of the safety function can only result in slight (usually
temporary) injuries (see also Section 6 ). In case of doubt, the "Safe pulse block" should always be used.

Note: The optional filter is only required in environments with heavy interference.


To implement the safety function STO, the digital input is parameterised to the function "Disable voltage".
With the safety function SS1 the digital input is assigned the function "Fast stop" (parameter P420[-01...-04])
and the fast stop time is set via parameter P426. It must be ensured that the drive is brought to standstill within
the parameterised fast stop time.

NOTE

As a maximum, this example achieves Safety Category 1 or Performance Level c. This circuit
version is not SIL-capable

(See Section 6).

DIN1 ...

GND

DIN4

40

24

24V

Reset

24V

Frequency inverter

optional

Emergency stop button

Reset circuit

Safety output

Use of a
digital input

STO:

P420[-01...-04]=10, "Disable voltage"

SS1:

P420[-01...-04]=11, "Fast stop"

Filter

for

OSSD

Shielded cable to eliminate
errors as per

DIN EN ISO 13849-2

Supply voltage

Input circuit
with short-
circuit
detection