42

BU 0530 GB-3712

Parameter

Setting value / Description / Note

Device

Supervisor

Parameter set

P434

[-01]

...

[-05]

Digital output function

(Digital output function)

SK 540E and

above

P

0 ... 39

{ [-01] = 1 }

{ [-02] = 7 }

all other { 0 }

Up to 5 outputs (2 of which are relays), which can be freely programmed with digital functions are
available in the SK 54xE. These can be seen in the following table.

[-01] = Output 1 / MFR1, relay output 1: external brake, (default),

Terminals 1/2

[-02] = Output 2 / MFR2, relay output 2: Fault, (default),

Terminals 3/4

[-03] = Output 3 / DOUT1, digital output 1: No function, (default),

Terminal 5

[-04] = Output 4 / DOUT2, digital output 2: No function, (default),

Terminal 7

6

[-05] = Output 5 / DOUT3, digital output 3: No function, (default),

Terminal 27

a

P441

Relay 2 function

(Output 2 function (Relay 2 - MFR2))

up to

SK 535E

P

0 ... 39

{ 7 }

Control terminals 3/4: Functions are identical to P434!

P450

Relay 3 function

(Function output 3 (DOUT1))

)

from SK 520E

to SK 535E

P

0 ... 39

{ 0 }

Control terminals 5/40: Functions are identical to P434! Digital output, 15V against DGND (for
SK 5x5E devices, deviations of the signal level are possible).

P455

Relay 4 function

(Function output 4 (DOUT2))

from SK 520E

to SK 535E

P

0 ... 39

{ 0 }

Control terminals 7/40: Functions are identical to P434! Digital output, 15V against DGND (for
SK 5x5E devices, deviations of the signal level are possible).

P470

Digital input 7

(Digital input 7)

from SK 520E

to SK 535E

0 ... 74

{ 0 }

No function as factory setting, control terminal 27 (DIN7)

Various functions can be progr

ammed. These can be found in the tables for P420…P425.

P559

DC Run-on time

(DC run-on time)

S

P

0.00 ... 30.00 s

{ 0.50 }

Following a stop signal and the braking ramp, a direct current is briefly applied to the motor to
fully bring the drive to a stop. Depending on the inertia, the time for which the current is applied
can be set in this parameter.

The current level depends on the previous braking procedure (current vector control) or the static
boost (linear characteristic).

6

Digital input 7 (DIN7) can also be used as digital output 3 (DOUT3 / Binary output 5). It is recommended that either an input function (P420 [-07] or an out-

put function (P434 [-05]) is parameterised. However, if and input function and an output function are parameterised, a High signal from the output function will
result in the activation of the input function. This IO-exclusion is hence used as a kind of "flag". This also applies for digital input 8 (DIN8) and digital output 2
(DOUT2 / binary output 4).