Functional safety with NORD SK 500E frequency inverters

32

BU 0530 GB-3712



In deviation from the illustration above, from size
5 and above, the position of terminal block X8 for
the connection of the safe pulse block is located
on the underside of the device (motor connection
side).

Connection data:

Frequency inverter

Sizes 5 ... 7

Rigid cable cross-section

0.2 … 6mm²

Flexible cable cross-section

0.2 … 4mm²

AWG standard

AWG 24-10

Tightening torque

for screw terminals

0.5 … 0.6Nm

Nominal ratings of safe pulse block

Terminal X8:86

(output - provision of +24V)

+24 V

(max. 300mA)

Terminal X8:87

GND

Terminal X8:89

(Input: “Safe pulse block”)

+24 V ± 25%

100mA (AV)

(Size 5 - 6)

140mA (AV)

(Size 7)

400mA (peak)

after switching-on or after

a test pulse from an OSSD

Terminal X8:88

GND