Terminal block x5 – digital in – NORD Drivesystems BU0530 User Manual

Page 34

Advertising
background image

Functional safety with NORD SK 500E frequency inverters

34

BU 0530 GB-3712

3.4.4

Details of the "Digital inputs" control connections

NOTE

AGND and DGND are common reference potentials for analog or digital inputs.

5V / 15V can be collected by several terminals if required. The sum of collected currents must
not exceed 250mA / 150mA.

Terminal block X5

– Digital In

Relevance

SK 500E

SK 505E

SK 510E

SK 511E

SK 515E

SK 520E

SK 530E

SK 535E

SK 540E

SK 545E

Terminals X5:

21

22

23

24

25

42

40

41

DIN1

DIN2

DIN3

DIN4

DIN5

VO 15V

GND / 0V

VO 5V

Designation

Terminal Function

[factory setting]

Data

Description / wiring suggestion

Parameter

up to
SK

535E

21

Digital input 1

[ON right]

7.5...30V, R

i

=6.1k

Not suitable for
thermistor evaluation.

HTL encoders can only
be connected to DIN2
and DIN4

Limiting frequencies:

max.

10 kHz

min.

15 Hz

Each digital input has a reaction time
o

f ≤ 5ms.

Control with internal 15V:

21

22

23

24

25
42

40

41

15V

motor - PTC

Control with external 7.5-30V:

21

22

23

24

25
42

40

41

7.5

… 30V

motor - PTC

GND / 0V

P420

22

Digital input 2

[ON left]

P421

23

Digital input 3

[parameter set bit0]

P422

24

Digital input 4

[Fixed frequency 1,

P429]

P423

25

Digital input 5

[no function]

2.5...30V, R

i

=2.2k

Not suitable for
evaluation of a safety
device.

Suitable for thermistor
evaluation with 5V.

NOTE: For the motor
thermistor P424 = 13
must be set.

P424

42

15V supply voltage
output

15V

20%

Supply voltage provided by the
frequency inverter for connection to
the digital inputs or the supply of a
10-30V encoder.

40

Reference potential
for digital signals

0V digital

Reference potential

41

5V supply voltage
output

5V

20%

Voltage supply for motor-PTC