3 Assembly and installation

BU 0530 GB-3712

33

3.4.3

Details of the "Safe pulse block" control connections

NOTE

As delivered, for commissioning without safety switching device, terminals 87-88 and 86-89 are
bridged. In order to be able to use the safety function, the bridges must be removed.

Terminal block X8

– Safe pulse lock (not with 115V devices)

Relevance

SK 500E

SK 505E

SK 510E

SK 511E

SK 515E

SK 520E

SK 530E

SK 535E

SK 540E

SK 545E

Terminal X8:

86

87

88

89

VO_S 15V

VO_S 0V

VI_S 0V

VI_S 24V

Designation

Terminal Function

[factory setting]

Data

Description / wiring suggestion

Parameter

up to SK
535E

SK 540E

and above

86

Supply voltage

15V

20%

When setting-up without using a
safety function, wire directly to V_IS
24V.

P420 et

seqq.

P420 [-

…]

87

Reference potential

88

Reference potential

24V

25%,

≤140mA

See technical data in
BU0530!

Fail-safe input

89

Input,

safe pulse lock

Relevance

SK 500E

SK 505E

SK 510E

SK 511E

SK 515E

SK 520E

SK 530E

SK 535E

SK 540E

SK 545E

Terminal X8:

86

87

88

89

VO_S 24V

VO_S 0V

V_S 0V

VI_S 24V

Designation

Terminal Function

[factory setting]

Data

Description / wiring suggestion

Parameter

up to SK
535E

SK 540E

and above

86

Supply voltage

18-30V, each to VI
24V

When setting-up without using a
safety function, wire directly to V_IS
24V.

P420 et

seqq.

P420 […]

87

Reference potential

88

Reference potential

24V

25%, ≤140mA

See technical data in
BU0530!

Fail-safe input

89

Input,

safe pulse lock