3 Assembly and installation

BU 0530 GB-3712

37

Relevance

SK 500E

SK 505E

SK 510E

SK 511E

SK 515E

SK 520E

SK 530E

SK 535E

SK 540E

SK 545E

Terminals X5:

21

22

23

24

39

38

44

40

DIN1

DIN2

DIN3

DIN4

TF-

TF+

VI 24V

GND / 0V

Designation

Terminal Function

[factory setting]

Data

Description / wiring suggestion

Parameter

SK 540E

and above

21

Digital input 1

[ON right]

7.5...30V, R

i

=6.1k

Not suitable for
thermistor evaluation.

HTL encoders can
only be connected to
DIN2 and DIN4

Limiting frequencies:

max.

10 kHz

min.

15 Hz

Each digital input has a reaction
time of ≤ 5ms.

21

22

23

24

39
38

44

40

motor - PTC

GND / 0V

18

… 30V

P420 [-01]

22

Digital input 2

[ON left]

P420 [-02]

23

Digital input 3

[parameter set bit0]

P420 [-03]

24

Digital input 4

[Fixed frequency 1,

P429]

P420 [-04]

39

Thermistor input -

potential isolated
thermistor input, which
cannot be disabled,
for monitoring the
motor temperature
with a PTC

38

Thermistor input +

44

24V supply voltage
input

18…30V
at least 800mA (input)

Voltage supply for the FI control unit.
This is essential for the function of
the frequency inverter.

40

Reference potential
for digital signals

0V digital

Reference potential