NORD Drivesystems BU0530 User Manual

Page 35

Advertising
background image

3 Assembly and installation

BU 0530 GB-3712

35

Relevance

SK 500E

SK 505E

SK 510E

SK 511E

SK 515E

SK 520E

SK 530E

SK 535E

SK 540E

SK 545E

Terminals X5:

21

22

23

24

25

44*

40

41

*

Terminal

44:

up to Size 4: VI

Size 5 and above:
VO

DIN1

DIN2

DIN3

DIN4

DIN5

V…

24V

GND /

0V

VO 5V

Designation

Terminal Function

[factory setting]

Data

Description / wiring suggestion

Parameter

up to
SK 535E

21

Digital input 1

[ON right]

7.5...30V, R

i

=6.1k

Not suitable for
thermistor evaluation.

HTL encoders can
only be connected to
DIN2 and DIN4

Limiting frequencies:

max.

10 kHz

min.

15 Hz

Each digital input has a reaction
time of ≤ 5ms.

21

22

23

24

25
44

40

41

18

… 30V

motor - PTC

GND / 0V

P420

22

Digital input 2

[ON left]

P421

23

Digital input 3

[parameter set bit0]

P422

24

Digital input 4

[Fixed frequency 1,

P429]

P423

25

Digital input 5

[no function]

Only S1

– S4

2.5...30V, R

i

=2.2k

Not suitable for
evaluation of a safety
device.

Suitable for thermistor
evaluation with 5V.

NOTE: For the motor
thermistor P424 = 13
must be set.

Above Size 5

Thermistor on
X13:T1/T2

P424

44

Size 1 to Size 4

VI 24V supply
voltage input

18…30V
at least 800mA (input)

Voltage supply for the FI control unit.
This is essential for the function of
the frequency inverter.

Size 5 and above

VO 24V supply
voltageoutput

24V ± 25%

max. 200mA (output)

Supply voltage provided by the
frequency inverter for connection to
the digital inputs or the supply of a
10-30V encoder.

The 24V control voltage is
generated by the FI, however it can
also be supplied via the terminals
X12:44/40. Supply via terminal
X5:44 is not possible.

40

Reference potential
for digital signals

0V digital

Reference potential

41

5V supply voltage
output

5V

20%

Voltage supply for motor-PTC

Advertising