NORD Drivesystems BU0530 User Manual

Page 41

Advertising
background image

4 Parameterisation

BU 0530 GB-3712

41

Parameter

Setting value / Description / Note

Device

Supervisor

Parameter set

P423

Digital input 4

(Digital input 4)

up to

SK 535E

0 ... 74

{ 4 }

Fixed frequency 1 (P429) as factory setting, control terminal 24 (DIN4)

Various functions can be programmed. These can be seen in the following table.

P425

Digital input 6

(Digital input 6)

From SK 520E

to SK 535E

0 ... 74

{ 0 }

No function as factory setting, control terminal 26 (DIN6)

Various functions can be programmed. These can be seen in the following table.

P426

Quick stop time

(Quick stop time)

P

0 ... 320.00 s

{ 0.10 }

Setting of the stop time for the fast stop function which can be triggered either via a digital input,
the bus control, the keyboard or automatically in case of a fault.

The emergency stop time is the time for the linear frequency decrease from the set maximum
frequency (P105) to 0Hz. If an actual setpoint <100% is being used, the emergency stop time is
reduced correspondingly.

P434

Relay 1 function

(Analog output 1 function (Relay 1

– MFR1))

up to SK

535E

P

0 ... 39

{ 1 }

Control terminals 1/2:Settings 3 to 5 and 11 work with a 10% hysteresis, i.e. the relay contact
closes (Function 11 opens) when the limit value is reached and opens (function 11 closes) when a
10% smaller value is undershot. This behaviour can be inverted with a negative value in P435.

Various functions can be programmed. These can be seen in the following table.