NORD Drivesystems BU0530 User Manual

Page 39

Advertising
background image

3 Assembly and installation

BU 0530 GB-3712

39

Relevance

SK 500E

SK 505E

SK 510E

SK 511E

SK 515E

SK 520E

SK 530E

SK 535E

SK 540E

SK 545E

Terminals X7:

73

74

26

27

5

7

44*

40

*

Terminal

44:

up to Size 4: VI

Size 5 and above:
VO

485+

RS485 -

DIN6

DIN7

DOUT1

DOUT2

V… 24V

GND / 0V

Designation

Terminal Function

[factory setting]

Data

Description / wiring suggestion

Parameter

up to
SK 535E

SK 540E

and above

73

Data cable RS485

Baud rate
9600…38400Baud
Termination resistor
R=120

BUS connection parallel to RS485
on RJ12 plug

NOTE: The termination resistance of
DIP switch 1 (see RJ12/RJ45) can
also be used for terminal 73/74.

P503

P509

P503

P509

74

26

Digital input 6

[no function]

7.5...30V, R

i

=3.3k

As described for terminal block X5,
DIN1 to DIN5.

Not suitable for the evaluation of a
motor thermistor.

P425

P420 [-06]

27

Digital input 7

[no function]

P470

P420 [-07]

Only SK 54xE

Alternatively:

Output 5 (DOUT3)

[no function]

Digital output

S1 to S4

18-30V according to
VI 24V, max. 20mA,

max. 100k

load

Above Size 5

DOUT1 and DOUT2:

24V, max. 200mA

max. 100k

load

With SK 54xE the digital input
(DIN7) can also be used as a digital
output (DOUT3).

If P434 [-05] and P420 [-07] are
parameterised with functions, a High
signal of the DOUT function results
in a High signal for the DIN function.

P434 [-05]

5

Output 3 (DOUT1)

[no function]

For evaluation in a control system.
The scope of functions corresponds
to that of the relay (P434).

P450

P434 [-03]

7

Output 4 (DOUT2)

[no function]

P455

P434 [-04]

Only SK 54xE

Alternatively:

Digital input 8

[no function]

7.5...30V, R

i

=3.3k

With SK 54xE the digital output
(DOUT2) can also be used as a
digital input (DIN3).

If P434 [-04] and P420 [-10] are
parameterised with functions, a High
signal of the DOUT function results
in a High signal for the DIN function.

P420 [-10]

44

Size 1 to Size 4

VI 24V supply
voltage input

18…30V
at least 800mA (input)

Voltage supply for the FI control unit.
This is essential for the function of
the frequency inverter.

Size 5 and above

VO 24V supply
voltageoutput

24V ± 25%

max. 200mA (output)

Supply voltage provided by the
frequency inverter for connection to
the digital inputs or the supply of a
10-30V encoder.

The 24V control voltage is
generated by the FI, however it can
also be supplied via the terminals
X12:44/40. Supply via terminal
X7:44 is not possible.

40

Reference potential
for digital signals

0V digital


Advertising