4 Parameterisation

BU 0530 GB-3712

43

List of the functions or the digital inputs P420 ... P425, P470 which are relevant to "Functional safety"

Value Function

Description

Signal

00

No function

Input switched off.

-----

10

Disable voltage

7

The FI output voltage is switched off; the motor runs down freely.

Low

11

Fast stop

³

The FI reduces the frequency according to the programmed fast stop time
P426.

Low


List of possible functions for the relays and digital outputs P434, P441, P450, P455

Valu

e

Function

Description

Signal*

00

No function

Input switched off.

Low

01

External brake

For the control of a mechanical brake on the motor. The relay switches at
a programmed absolute minimum frequency (P505). For typical brakes a
setpoint delay of 0.2 … 0.3 seconds (see also P107) should be
programmed.

A mechanical brake can be directly AC switched. (Please note the tech-
nical specifications of the relay contacts)

High

07

Fault

General fault message, fault is active or not yet acknowledged.

Error

– contact opens

(ready

– contact closes)

Low

39

STO inactive

The relay / bit deactivates if STO or the Safe Stop are active.

High

* For relay contacts (High = "Contact closed", Low = "Contact open")


A complete list of all possible functions can be found in Manual BU 0500 GB.