5 Frequency inverters - settings and control elements

5.1 Frequency inverter bus parameters

To operate the inverter with the DeviceNet protocol, the bus must be connected to the Master and some
settings must be made on the frequency inverter.

With the DeviceNet protocol, the inverter parameters are mapped onto DeviceNet objects in the range 100 to 109:

- Class = 100 + parameter number / 100
- attribute = parameter number % 100
- instance = sub-index +1

or

- Parameter number = (class – 100) * 100 + attribute
- sub-index = instance -1

The frequency inverter can always be parameterised. Control of the inverter via DeviceNet can be activated by
setting parameter P509 to value 18, 19 or 20 (SK 500E: value 7). (see below)

5.1.1

Control terminal parameters

Parameter

Setting value / Description / Note

Comments

P480

.. - 01

...

.. - 12

Function Bus I/O In Bits

The Bus I/O In Bits are perceived as digital inputs. They can be set to the same functions as the digital
inputs (See P420…of the respective FI manual).

0 ... 72

[ 0 ]

[01]= Bus I/O In Bit 0

[02]= Bus I/O In Bit 1

[03]= Bus I/O In Bit 2

[04]= Bus I/O In Bit 3

[05]= Bus I/O In Bit 4

[06]= Bus I/O In Bit 5

[07]= Bus I/O In Bit 6

[08]= Bus I/O In Bit 7

[09]= Flag 1 (only SK 500E)

[10]= Flag 2 (only SK 500E)

[11]= Bit 8 BUS control word (only for SK 500E)

[12]= Bit 9 BUS control word (only for SK 500E)

P481

.. - 01

...

.. - 10

Function Bus I/O Out Bits

The bus I/O Out bits are perceived as multi-function relay outputs. They can be set to the same functions
as the digital inputs (See P434…of the respective FI manual).

0 ... 39

[ 0 ]

[01]= Bus I/O Out Bit 0

[02]= Bus I/O Out Bit 1

[03]= Bus I/O Out Bit 2

[04]= Bus I/O Out Bit 3

[05]= Bus I/O Out Bit 4

[06]= Bus I/O Out Bit 5

[07]= Bus I/O Out Bit 6 / Flag 1

[08]= Bus I/O Out Bit 7 / Flag 2

[09]= Bit 10 BUS status word (only for SK 500E)

[10]= Bit 13 BUS status word (only for SK 500E)